D1U4CS-W-2200-12-HxxC Series
AC/DC Front End Power Supply
PRODUCT OVERVIEW
The D1U4CS-W-2200-12-HxxC
is a 2200 Watt, power-factor-corrected (PFC) front-end power supply for hot-
swapping redundant systems. The main output is 12V with standby output of 5V or 3.3V. Packaged in 1U low profile,
it is designed to deliver reliable bulk power to servers, workstations, storage systems or any 12V distributed power
architecture systems requiring high power density. The highly efficient electrical and thermal design with internal
cooling fans supports reliable operation conditions. The D1U4CS-W-2200-12-HxxC is designed to auto-recover from
overtemperature fault. Status information is provided with front panel LEDs, logic signals and I
2
C management inter-
face. Four units can be packaged into an optional 19” 1U power shelf to provide up to 8.8kW of power.
SELECTION GUIDE
Model Number
D1U4CS-W-2200-12-HC4C
D1U4CS-W-2200-12-HC3C
D1U4CS-W-2200-12-HA4C
D1U4CS-W-2200-12-HA3C
Power Output
High Line AC
2200W
2200W
2200W
2200W
Power Output
Low Line AC
1100W
1100W
1100W
1100W
Main
Output
12.12V
12.12V
12.12V
12.12V
Standby
Output
3.3V
3.3V
5V
5V
Airflow
Back to front
Front to back
Back to front
Front to back
FEATURES
2200W (220Vac), 1100W (110Vac)
Output Power
ed to Climate Savers Computing
Certifi
Initiative
SM
and 80 PLUS® Gold efficiency
Main Output, 3.3V or 5V Standby Output
12V
sized; dimensions 14.0” x 4.0” x 1.6”
1U
Watts per cubic inch density
24.5
redundancy capable,
N+1
including hot-docking
Active Current Sharing on main output
Over-voltage, Over-current,
Over-temperature protection
Internal cooling fans (variable speed)
Bus Interface, PSMI compliant
I²C
compliant
RoHS
Optional 1U x 19” Power-Shelf
INPUT CHARACTERISTICS
Parameter
Input Voltage Operating Range
Input Frequency
Turn-on Input Voltage
Turn-off Input Voltage
Maximum Input Current
Inrush Current
Power Factor
Conditions
Low Line AC
High Line AC
Ramp up
Ramp down
Low Line AC 90Vac
High Line AC 180Vac
Cold start between 0-1msec
Output load >90%
Output load >50%
Min.
90
180
47
81
70.5
Typ.
Max.
140
264
63
89
78
13
13
16.5
Units
Vac
Hz
Vac
Arms
Apk
60
0.95
0.95
OUTPUT VOLTAGE CHARACTERISTICS
Output
Voltage
Parameter
Voltage Set Point Accuracy
Line and Load Regulation
Ripple Voltage & Noise
Output Current
Load Capacitance
Voltage Set Point Accuracy
Line and Load Regulation
Ripple Voltage & Noise
Operating Range
Load Capacitance
Voltage Set Point Accuracy
Line and Load Regulation
Ripple Voltage & Noise
Operating Range
Load Capacitance
Conditions
Min.
11.76
Typ.
12.12
Max.
12.48
120
180
30000
Units
Vdc
mV p-p
A
μF
Vdc
mV p-p
A
μF
Vdc
mV p-p
A
μF
12V
20MHz Bandwidth
0
5
20MHz Bandwidth
4.85
0
3.3
20MHz Bandwidth
3.2
0
5Vsb
5.15
50
5
10000
3.4
50
6
10000
3.3Vsb
1 Ripple and noise are measured with 0.1 uF of ceramic capacitance and 10 uF of tantalum capacitance on each of the power supply outputs. The output
noise requirements apply over a 0 Hz to 20 MHz bandwidth. A short coaxial cable with 50ohm scope termination is used.
For full details go to
www.murata-ps.com/rohs
www.murata-ps.com
17 Aug 2010
email: toronto@murata-ps.com
CPS_D1U4CS-2200-12-HxxC.A04
Page 1 of 5