欢迎访问ic37.com |
会员登录 免费注册
发布采购

NIFP-AI-102 参数 Datasheet PDF下载

NIFP-AI-102图片预览
型号: NIFP-AI-102
PDF下载: 下载PDF文件 查看货源
内容描述: 模拟量输入模块的的Compact FieldPoint和FieldPoint的 [Analog Input Modules for Compact FieldPoint and FieldPoint]
分类和应用:
文件页数/大小: 4 页 / 615 K
品牌: NI [ NATIONAL INSTRUMENTS CORPORATION ]
 浏览型号NIFP-AI-102的Datasheet PDF文件第2页浏览型号NIFP-AI-102的Datasheet PDF文件第3页浏览型号NIFP-AI-102的Datasheet PDF文件第4页  
Analog Input Modules for
Compact FieldPoint and FieldPoint
NI [c]FP-AI-100, NI [c]FP-AI-102,
NI [c]FP-AI-110, NI [c]FP-AI-111
• 8 or 16 voltage or current inputs
±120 V input range, maximum
0 to 20, 4 to 20 mA input ranges
• Built-in signal conditioning
50, 60, and 500 Hz noise rejection
• 12 and 16-bit resolution
• Software-configurable input ranges per
channel
• 2,300 V
rms
bank isolation for transient
overvoltage protection
• Hot-swappable with autoconfiguration
• -40 to 70 °C operating range
NEW
Module
[c]FP-AI-100
[c]FP-AI-102
[c]FP-AI-110
[c]FP-AI-111
Input Channels
8
8
8
16
Resolution
12 bits
12 bits
16 bits
16 bits
Input Type
Voltage
Current
Voltage
Voltage
Current
Current
Input Ranges
(Software Configurable per Channel)
±1 V, ±5 V, ±15 V, ±30 V, 0 to 1 V, 0 to 5 V, 0 to 15 V, 0 to 30 V
0 to 20 mA, 4 to 20 mA, ±20 mA
±20 V, ±60 V, ±120 V, 0 to 20 V, 0 to 60 V, 0 to 120 V
±60 mV, ±300 mV, ±1 V, ±5 V, ±10 V, 0 to 1 V, 0 to 5 V, 0 to 10 V
0 to 20 mA, 4 to 20 mA, ±20 mA
0 to 20 mA, 4 to 20 mA, ±20 mA
50/60 Hz Noise Filter
(software selectable)
(software selectable)
All-Channel
Update Rate
360 Hz
360 Hz
5 Hz to 0.66 Hz
(rate varies with filter settings)
3 Hz to 0.83 Hz
(rate varies with filter settings)
Overview
The National Instruments [c]FP-AI-1xx devices are versatile analog
input modules for Compact FieldPoint and FieldPoint that can be
used to measure voltages ranging from the millivolt level to the
120 V high-voltage level in applications such as battery-pack
monitoring, fuel-cell testing, and general measurement from
transducers. These modules can also measure 0 to 20 or 4 to 20 mA
current loops from industrial sensors and transmitters. All the
modules include overranging and onboard diagnostics to ensure
trouble-free installation and maintenance. The modules measure and
linearize signals on-board to return scaled values to your control
or monitoring software. The [c]FP-AI-1xx modules come with
NIST-traceable calibration certificates, ensuring accurate and reliable
analog measurements.
Smart I/O Modules
With [c]FP-AI-1xx analog input modules, you can directly connect to
your industrial sensors or units under test and get high-accuracy
measurements. The I/O modules filter, calibrate, and scale raw sensor
signals to engineering units, as well as performing self-diagnostics to
look for problems with the module or the wiring. With FieldPoint
modules, your software application reads a linearized, calibrated, and
scaled value from the I/O module, eliminating the error-prone step of
converting binary values to voltage or current values. For increased
accuracy and noise rejection, the [c]FP-AI-110 and [c]FP-AI-111 use a
16-bit delta-sigma ADC with an integrated lowpass filter on each
channel, which you can configure for 50 Hz, 60 Hz, or no rejection.
With high-accuracy 12-bit ADCs or 16-bit delta-sigma ADCs on the
I/O modules, you also get instrument-quality measurements on an
industrially rugged, distributed, embedded system.
[c]FP-AI-1xx modules offer a variety of update rates to fit your
application, ranging from 0.66 to 360 Hz. These rates vary based on
the module used and on the noise filter settings selected on the
module. Overall data throughput depends on software loop speeds
and network speeds. With overranging and underranging, the
[c]FP-AI-1xx analog input modules can measure inputs or sensors
that are not calibrated to standard ranges. For example, when
configured for an input range of 4 to 20 mA, the modules actually
measure inputs from 3.5 to 21 mA.