欢迎访问ic37.com |
会员登录 免费注册
发布采购

FNP1500-12G 参数 Datasheet PDF下载

FNP1500-12G图片预览
型号: FNP1500-12G
PDF下载: 下载PDF文件 查看货源
内容描述: 前端和FNR - 3电源架数据表 [Front-Ends & FNR-3 Power Shelves Data Sheet]
分类和应用:
文件页数/大小: 17 页 / 494 K
品牌: POWER-ONE [ POWER-ONE ]
 浏览型号FNP1500-12G的Datasheet PDF文件第6页浏览型号FNP1500-12G的Datasheet PDF文件第7页浏览型号FNP1500-12G的Datasheet PDF文件第8页浏览型号FNP1500-12G的Datasheet PDF文件第9页浏览型号FNP1500-12G的Datasheet PDF文件第11页浏览型号FNP1500-12G的Datasheet PDF文件第12页浏览型号FNP1500-12G的Datasheet PDF文件第13页浏览型号FNP1500-12G的Datasheet PDF文件第14页  
FNP1500/1800 Front-Ends
& FNR-3 Power Shelf Data Sheet
Paralleling Front-Ends:
For parallel use in minimal configuration systems, only the inhibit pins must be shorted to logic GND. All other pins can be left
open. The power supplies will share the output current automatically (droop current share).
2
For parallel applications without I C bus, but the use of all other features, it is recommended to connect all logic GND’s on a
backplane together, to connect all V
o2
-, all V
o2
+ and to leave the internal GND’s open.
The sense wires can be left open or connected to a common load point, the synch-start pin can be left open or connected to a
2
synch-start circuit, the inhibit pins can be connected together or used individually. All I C signals (T1-T5, S1, and S2) can be left
open.
Use of a small foil capacitor > 3µF directly at the power outputs of each unit is recommended in order to prevent voltage drops at
the hot plug. For additional information on paralleling see the following Rack (Power Shelf) section.
Racks
(FNR-3-12G and FNR-3-48G Power Shelves)
Each rack (power shelf) is 1U high with backplane and designed for up to three front-end models in parallel or in n+1 operation.
Each power shelf has:
Massive copper bus bars for low-loss current distribution.
Output terminals with two M4-screws on each power tab.
Two fast-on contacts for system earthing.
Address coding over five pole DIP switch on each unit, 37-pin D-Sub connector with I
2
C-lines, monitoring signals and
support functions.
Provides a start-up synchronization circuit and EMV filters.
FNR-3-12G and FNR-3-48G Power Shelf Front View
Overall Mechanical Dimensions (FNR-3-12G and FNR-3-48G Power Shelves)
FNR-3 Mechanical Data (W, H, D)
17.7” (449.6 mm) x 1.7” (43.1 mm) x 13” (330.2 mm)
MCD10074 Rev. 1.2, 15-Apr-10
Page 10 of 17
www.power-one.com