欢迎访问ic37.com |
会员登录 免费注册
发布采购

DD12.9111.111 参数 Datasheet PDF下载

DD12.9111.111图片预览
型号: DD12.9111.111
PDF下载: 下载PDF文件 查看货源
内容描述: IEC设备入口C14与过滤器,保险丝座1或2杆,线路开关二极 [IEC Appliance Inlet C14 with Filter, Fuseholder 1- or 2-pole, Line Switch 2-pole]
分类和应用: 过滤器开关
文件页数/大小: 5 页 / 723 K
品牌: SCHURTER [ SCHURTER INC. ]
 浏览型号DD12.9111.111的Datasheet PDF文件第2页浏览型号DD12.9111.111的Datasheet PDF文件第3页浏览型号DD12.9111.111的Datasheet PDF文件第4页浏览型号DD12.9111.111的Datasheet PDF文件第5页  
Power Entry Modules with Line Filter
IEC Appliance Inlet C14 with Filter, Fuseholder 1- or 2-pole, Line Switch 2-pole
DD2
Standard- or Medical-Filter
C14
70° C
Description
- Panel Mount:
Screw-on from front side
- 4 Functions:
Appliance Inlet Protection class I, Line Switch 2-pole, Fuseholder for
fuse-links 5 x 20 mm 1- or 2-pole, Line filter in standard and medical
version
- Quick connect terminals 6.3 x 0.8 mm
- Alternative: version without line filter DD11
- Alternative: version for snap-in mounting KMF
Characteristics
- Ultra-compact design. Ideal for low profile designs
Aluminum case provides good shielding
- All single elements are already wired
- Fuse drawer meets requirements of medical standard IEC/EN 60601-1
The fuseholder is accessible from the equipment front
For added safety "Extra-Safe" fuse drawers are available
- Ideal for application with high transient loads
Designed for standard and medical applications
- Qualified for use in equipment according IEC/EN 60950
Approvals
Other versions on request
- VDE License Number: 40001522
- UL License Number: E72928
- Solder terminals
- Fuse drawer 1-pole, plus spare fuse case
- Fuse drawer 2-pole, with shorting bar
- Other rocker marking
- Line switch, illuminated
- Line switch 1-pole
- Medical version M80
- Class X1- and Y1-capacitors for enhanced withstand voltage
- Protection class II, 70°C
References
Weblinks
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
Dielectric Strength
1 - 10 A @ Ta 40 °C / 250 VAC; 50 Hz
1 - 8 A @ Ta 40 °C / 250 VAC; 60 Hz
standard < 0.5 mA (250 V / 60 Hz)
medical < 5 µA (250 V / 60 Hz)
> 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (1 min/50 Hz)
-25 °C to 85 °C
25/085/21 acc. to IEC 60068-1
from front side IP 40 acc. to IEC 60529
Suitable for appliances with protection
class 1 acc. to IEC 61140
Quick connect terminals 6.3 x 0.8 mm
Screw-on mounting: max 8 mm
Mounting screw torque max 0.5 Nm
Thermoplastic, black, UL 94V-0
Appliance-Inlet/-Outlet
C14 acc. to IEC/EN 60320-1
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 10 A,
Protection Class 1
1 or 2 pole, Shocksafe category PC2
acc. to IEC 60127-6,
for fuse-links 5 x 20 mm
5 x 20: 2 W (1 pole)/ 1.6 W (2-pole) per
pole
Admissible power acceptance at hig-
her ambient temperature see derating
curves
Rocker switch 2-pole, non-illuminated,
acc. to IEC 61058-1
Standard and Medical Version, IEC
60939, IEC 60601-1, UL 1283, UL 544,
EN 133 200, CSA C22.2 no. 8
> 2'000'000 h acc. to MIL-HB-217 F
Fuseholder
Allowable Operation Temp.
Climatic Category
Degree of Protection
Protection Class
Terminal
Panel Thickness s
Material: Housing
Rated Power Acceptance @
Ta 23 °C
Power Acceptance @ Ta >
23°C
Line Switch
Line Filter
MTBF
EMC Products