Power entry modules without line filter
IEC Appliance Inlet C14 with Fuseholder 1- or 2-pole and Voltage Selector
KE
Standard or Medical Fuse drawer
C14
70° C
Description
- Panel Mount:
Screw-on version from front or rear side, snap-in version from front
side
- 3 Functions:
Appliance Inlet Protection class I, Fuseholder with interchangeable fuse
drawer for Fuse-links 5 x 20 mm or 6.3 x 32 mm 1- or 2-pole, Voltage
Selectors (series-parallel)
- Quick connect terminals 4.8 x 0.8 mm
- Alternative: version with line filter CE
Characteristics
- Available with or without internal partial wired connections
- For added safety "Extra-Safe" fuse drawers are available
Fuse drawer meets requirements of medical standard IEC/EN 60601-1
The fuse drawer can only be opened with the aid of a tool
The fuseholder is accessible from the equipment front
- Qualified for use in equipment according IEC/EN 60950
Other versions on request
- For protection class II
Approvals
References
Weblinks
- VDE License Number: 40011908
- UL License Number: E93617
- CSA License Number: 38456
Technical Data
Ratings IEC
Ratings UL/CSA
Dielectric Strength
10 A / 250 VAC; 50 Hz
10 A / 125 VAC; 60 Hz
> 3 kVAC between L-N
> 4 kVAC between L/N-PE
(1 min/50 Hz)
-25 °C to 70 °C
from front side IP 40 acc. to IEC 60529
Suitable for appliances with protection
class 1 acc. to IEC 61140
Quick connect terminals 4.8 x 0.8 mm
Screw: max 8 mm
Mounting screw torque max 0.5 Nm
Snap-in: 1.5/2/2.5 mm
Thermoplastic, black, UL 94V-0
Appliance Inlet
C14 acc. to IEC/EN 60320-1,
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 10 A,
Protection Class 1
1 or 2 pole, Shocksafe category PC2
acc. to IEC 60127-6,
for fuse-links 5 x 20 or 6.3 x 32 mm
5 x 20: 2.5 W (1 pole)/ 2 W (2-pole) per
pole
6.3 x 32: 3.15 W (1 pole)/ 2.5 W (2-pole)
per pole
Admissible power acceptance at hig-
her ambient temperature see derating
curves
series-parallel, 4, 3 or 2 switch positions
or usable as 2-pole change-over switch
Fuseholder
Allowable Operation Temp.
Degree of Protection
Protection Class
Terminal
Panel Thickness s
Rated Power Acceptance @
Ta 23 °C
Power Acceptance @ Ta >
23°C
Voltage Selectors
Material: Housing
Connectors