欢迎访问ic37.com |
会员登录 免费注册
发布采购

BTE6035A4 参数 Datasheet PDF下载

BTE6035A4图片预览
型号: BTE6035A4
PDF下载: 下载PDF文件 查看货源
内容描述: 精密不锈钢压力变送器 [Precision stainless steel pressure transmitters]
分类和应用:
文件页数/大小: 8 页 / 122 K
品牌: SENSORTECHNICS [ SENSORTECHNICS GMBH ]
 浏览型号BTE6035A4的Datasheet PDF文件第1页浏览型号BTE6035A4的Datasheet PDF文件第2页浏览型号BTE6035A4的Datasheet PDF文件第3页浏览型号BTE6035A4的Datasheet PDF文件第5页浏览型号BTE6035A4的Datasheet PDF文件第6页浏览型号BTE6035A4的Datasheet PDF文件第7页浏览型号BTE6035A4的Datasheet PDF文件第8页  
BTE6000 / PTU6000 Series
Precision stainless steel pressure transmitters
Specification notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
IP 65 protection is given when the connector is locked with a rubber washer. For proper function the gage port is vented
to the atmosphere through the connector/cable assembly. Thus the cable end must have access to the ambient pressure.
The minimum supply voltage is directly proportional to the load resistance seen by the transmitter. For more details see the
load limitation diagram.
Proof pressure is the maximum pressure which may be applied without causing damage to the sensing element.
Thermal effects tested and guaranteed from 0 to 70°C relative to 25°C. All specifications shown are relative to 25°C.
Non-linearity refers to the
Best Straight Line
fit measured for offset, full scale span and 1/2 full scale span.
Long term stability is the change in output after one year or 1 million pressure cycles.
Span is the arithmetic difference in transmitter output signal measured at zero pressure and the maximum operating pressure.
Test are in accordance with EN61000-6-2, April 1999.
CE-labelling is in accordance with 89/336/EEC.
The pressure transmitters must not be used as safety accessories according to article 1, 2.1.3 of the directive 97/23/EC.
Available for pressure ranges from 1 bar (15 psi) absolute upwards only.
Other sealing materials are available on request.
ELECTROMAGNETIC CAPABILITY
8
Test conditions
Criterion Interference
Radiated, radio frequency
EN61000-4-3: Grade 3, 10 V/m, 80 to 1000 MHz
A
<1 %FSO
electromagnetic field immunity (RFI)
80 % AMC (1 kHz)
Electrical fast transient /
EN61000-4-4: Grade 3, ±2 kV
B
<1 %FSO
burst immunity (EFT)
Electrostatic discharge immunity
EN61000-4-2: Grade 4, ±8 kV, contact discharge
B
<1 %FSO
test (ESD)
Immunity to conducted disturbances EN61000-4-6: Grade 3, 0.15 to 80 MHz
A
<1 %FSO
induced by radio-frequency fields
10 V, 80 % AMC (1 kHz)
LOAD LIMITATION
0...20 mA output version
4...20 mA output version
1400
Ohm
1200
1000
800
600
400
200
operating
range
RECOMMENDED ACCESSORY
Plug
DIN EN 175301-803 A
and profile washer included
in delivery. For a complete connector/cable assembly
use order no.
ZK000110-x
(x=cable lenghts in m).
50
34
Profile washer
M3
31
dimensions in mm
0
5
10
15
20
25
30
35 V
supply voltage
Note:
For proper function of all gage devices the
gage port must be vented to the atmosphere
through the connector/cable assembly.
December 2008 / 102
4/8