Technical data
6.1
Input
Rated voltage
V
e rated
AC voltage range
Voltage* range DC
Connect/shutdown threshold
Overvoltage resistance
Rated line frequency; rated line frequency range
6EP1311-1SH03
Rated current
6EP1311-1SH13
I
e rated at Ve = 230 V
6EP1321-1SH03
6EP1322-1SH03
6EP1351-1SH03
6EP1352-1SH03
6EP1331-1SH03
6EP1332-1SH43
6EP1332-1SH52
Switch-on current limitation
(+25 °C)
6EP1311-1SH03
6EP1311-1SH13
6EP1321-1SH03
6EP1322-1SH03
6EP1351-1SH03
6EP1352-1SH03
6EP1331-1SH03
6EP1332-1SH43
6EP1332-1SH52
1-phase 100 - 240 V AC wide-range input
85 … 264 V AC
110 to 300 V DC
Typ. 80 V/70 V
2,3 ×
V
e rated, 1.3 ms
50/60 Hz; 47 to 63 Hz
0.20 A
0.43 A
0.29 A
0.67 A
0.35 A
0.70 A
0.36 A
0.69 A
0.99 A
< 30 A
< 55 A
< 30 A
< 55 A
< 30 A
< 55 A
< 30 A
< 50 A
< 30 A
6
I
2
t value
6EP1311-1SH03 0.4 A
2
s
6EP1311-1SH13 1.2 A
2
s
6EP1321-1SH03 0.4 A
2
s
6EP1322-1SH03 1.2 A
2
s
6EP1351-1SH03 0.4 A
2
s
6EP1352-1SH03
6EP1331-1SH03
6EP1332-1SH43
6EP1332-1SH52
1.2 A
2
s
0.4 A
2
s
1.2 A
2
s
1.3 A
2
s
Fuse
Miniature circuit breakers (IEC 898
)characteristic C 10 A
or characteristic B 16 A
>40 ms (for 187 V)
Built-in line-side fuse
Required protection in the mains supply
conductor
Mains buffering at Ia rated
LOGO!Power
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
23