Commercial
Model
GSC25A
Medical
Model
GSM25A
Output No.
1
2
3
Output
+ 5.1 V
+12 V
- 12 V
+5V
+15 V
- 15 V
+5.1 V
+24 V
-12 V
Current
2.5 A
1.5 A
0.2 A
2.5 A
1.5 A
0.2 A
2.5 A
1.0 A
0.2 A
Load
Regulation
1%
4%
1%
1%
4%
1%
1%
4%
1%
Initial Setpoint
Tolerance
1%
3%
4%
1%
3%
4%
1%
3%
4%
OVP
Setting
6.2 ± 0.6 V
Ripple and
Noise
1%
1%
1%
Notes
A
A
B
A
A
B
A
A
B
GSC25B
GSM25B
1
2
3
6.2 ± 0.6 V
1%
1%
1%
GSC25D
GSM25D
1
2
3
6.2 ± 0.6 V
1%
1%
1%
A. To maintain proper regulation on output 2, +5.1 V current must be at least 1⁄4 and not greater than 5 times V2 current. V1 must be adjusted within 1% of 5.1 V
to maintain full load regulation on V2.
B. Thermal foldback type current limit
C. Add “G” suffix to model number for RoHS compliant model.
GSC25/GSM25 MECHANICAL SPECIFICATIONS
ENVIRONMENTAL SPECIFICATIONS
Temperature (A)
Humidity (A)
Shock (B)
Altitude
Vibration (C)
OPERATING
See individual specs.
0 to 95% RH
20 g
pk
-500 to 10,000 ft
1.5 g
rms’
0.003 g
2
/Hz
NON-OPERATING
-40 to +85°C
0 to 95% RH
40 g
pk
-500 to 40,000 ft
5 g
rms’
0.026 g
2
/Hz
A. Units should be allowed to warm up/operate under
non-condensing conditions before application of power.
B. Shock testing—half-sinusoidal, 10 ± 3 ms duration, ± direction,
3 orthogonal axes, total 6 shocks.
C. Random vibration—10 to 2000Hz, 6dB/octave roll-off from 350
to 2000Hz, 3 orthogonal axes. Tested for 10 min./axis operating and
1 hr./axis non-operating.
SL Power Electronics Corp. 6050 King Drive, Bldg. A, Ventura, CA 93003, USA. Phone:(805) 486 4565 Fax:(805) 487 8911 Email: info@slpower.com Rev. 4/22/08.
Data Sheet © 2008 SL Power Electronics Corp. The information and specifications contained in this data sheet are believed to be correct at time of publication.
However, SL Power Electronics accepts no responsibility for consequences arising from reproduction errors or inaccuracies. Specifications are subject to change without
notice.