Dual RPM-Based PWM Fan Controller with Hardware Thermal Shutdown  
Datasheet  
to control the fan drive output independently (or jointly) by programming up to eight pairs of  
temperature and drive setting entries.  
The user programs the look-up table based on the desired operation. If the RPM based Fan Speed  
Control Algorithm is to be used (see Section 5.5), then the user must program an RPM target for each  
temperature setting of interest. Alternately, if the RPM based Fan Speed Control Algorithm is not to be  
used, then the user must program a drive setting for each temperature setting of interest.  
If the measured temperature on the External Diode channel meets or exceeds any of the temperature  
thresholds for any of the temperature columns (see Appendix B), the fan output will be automatically  
set to the desired setting corresponding to the exceeded temperature. In cases where multiple  
temperature channel thresholds are exceeded, the highest fan drive setting will take precedence.  
When the measured temperature drops to a point below a lower threshold minus the hysteresis value,  
the fan output will be set to the corresponding lower set point.  
Figure 5.3 shows an example of this operation using temperature - drive setting pairs for a single  
channel.  
See Appendix B for examples of the Look Up Table operation.  
Fan  
Setting  
Temp  
T8  
T8 - Hyst  
S8  
S7  
T7  
T7 - Hyst  
T6  
S6  
T6 - Hyst  
T5  
S5  
T5 - Hyst  
T4  
S4  
T4 - Hyst  
Averaged  
Temperature  
T3  
S3  
S2  
Fan  
Setting  
T3 - Hyst  
T2  
T2 - Hyst  
S1  
Measurement taken  
T1  
Time  
Figure 5.3 Fan Control Look-Up Table Example  
SMSC EMC2104  
Revision 1.74 (05-08-08)  
DATA2S7HEET