欢迎访问ic37.com |
会员登录 免费注册
发布采购

IQ65033QMA10 参数 Datasheet PDF下载

IQ65033QMA10图片预览
型号: IQ65033QMA10
PDF下载: 下载PDF文件 查看货源
内容描述: 四分之一砖ATCA电源接口模块 [Quarter-Brick ATCA Power Interface Module]
分类和应用:
文件页数/大小: 15 页 / 1188 K
品牌: SYNQOR [ SYNQOR WORLDWIDE HEADQUARTERS ]
 浏览型号IQ65033QMA10的Datasheet PDF文件第6页浏览型号IQ65033QMA10的Datasheet PDF文件第7页浏览型号IQ65033QMA10的Datasheet PDF文件第8页浏览型号IQ65033QMA10的Datasheet PDF文件第9页浏览型号IQ65033QMA10的Datasheet PDF文件第11页浏览型号IQ65033QMA10的Datasheet PDF文件第12页浏览型号IQ65033QMA10的Datasheet PDF文件第13页浏览型号IQ65033QMA10的Datasheet PDF文件第14页  
Input:  
Outputs:  
Current:  
Package:  
36-75 V  
5.0 V/ 3.3 V  
10 A  
Quarter-brick  
Technical Specification  
In the event of a gradual loss of input voltage (see Figure C), the  
main -48V output will shut down 100ms after the beginning of  
the hold-up event. The -48V output will enter a hiccup mode of  
operation for input voltages below the Hold-up Arm Threshold.  
Management power will continue to run until the input voltage  
(plus 0V to 1.2V for the ORing MOSFETs) decays to the manage-  
ment power under-voltage turn-off threshold.  
Hot Swap – Shutdown Timing: In the event of a sudden loss  
of input voltage (see Figure B), a hold-up event will be triggered.  
When the output voltage (plus a diode drop for the hot-swap body  
diode) decays to the management power under-voltage turn-off  
threshold, the main -48V output and the 3.3V/5.0V outputs will  
shut down simultaneously.  
48V  
Input voltage  
0
Holdup time, tH  
Holdup event  
48V  
0
39 V  
typ.  
(Depends  
on version)  
34.6 V  
typ.  
Payload output 48V  
3.3V  
0
Management power  
Alarm  
(Pull-up voltage lost)  
0
Figure B: Sudden Loss of Input Power  
48V  
38.4 V  
typ.  
38.9 V  
typ.  
34.0  
(Depends  
on version)  
Higher of A/B input feed voltages  
RTN A/B - (-48V_A/B)  
V
0
Holdup event  
48V  
Output is off after  
delay if input  
38.5 V  
typical  
(Depends  
on version)  
voltage doesn’t  
recover above  
38.9V typ.  
-48V output voltage  
VRTNOUT - (-48V_OUT)  
100ms  
0
Management power turned  
3.3V  
off at higher of ENABLE  
threshold or MP UVLO.  
Management power output  
(3.3V) - LOGIC_GND  
0
Alarm - (LOGIC_GND)  
(Pullup voltage lost)  
Figure C: Gradual Loss of Input Power  
Product # IQ65033QMA10  
Phone 1-888-567-9596  
www.synqor.com  
Doc.# 005-IQ5033S Rev. G  
05/04/09  
Page 10