General Description
System Sensor 1012B ionization and 2012B photoelectronic
detectors are designed primarily for applications where
low-voltage Class 2 wiring may be used. These detectors
are self-resetting and offer an 85dB alarm horn. An
external push button provides a test of the detectors’
alarm function. Up to 12 units can be interconnected so
that if one detector alarms, all detectors alarm. A normally
open auxiliary alarm relay is available for controlling
external functions. A visible LED indicator flashes once
every 40 seconds in standby and rapidly in alarm when
detecting smoke. The detectors offer low-voltage operation
and a tamper-proof feature. Screw terminals and a
mounting bracket are provided for easy installation.
RED (+)
A77-727-O1
BLACK
12VDC POWER
12OVAC
GRAY (–)
SUPPLY
BLACK
POWERS UP TO
16 DETECTORS
GROUND
SIGNAL
GROUND
SIGNAL
(+) (–)
POWER INPUT
(+) (–)
POWER INPUT
(+) (–)
POWER INPUT
AUXILIARY
AUXILIARY
AUXILIARY
GROUND
SIGNAL
GROUND
SIGNAL
(+) (–)
POWER INPUT
(+) (–)
POWER INPUT
(+) (–)
POWER INPUT
GROUND
SIGNAL
GROUND
SIGNAL
AUXILIARY ALARM RELAY
AUXILIARY
AUXILIARY
AUXILIARY
INTERCONNECT UP TO
12 DETECTORS
WIRE
GAUGE 1 UNIT 2 UNITS 3 UNITS 4 UNITS 5 UNITS 6 UNITS 7 UNITS 8 UNITS 9 UNITS 10 UNITS 11 UNITS 12 UNITS
14AWG 5000
990
848
742
660
594
540
495
2970
1980
1485
1188
16AWG 3735
622
533
466
415
373
339
311
1867
1245
933
747
18AWG 2349
391
335
293
261
234
213
195
1174
783
587
469
MAXIMUM POWER BUS LENGTH IN FEET. GIVEN NUMBER OF
UNITS (MAXIMUM PER BUS) AND WIRE SIZE.
MAXIMUM INTERCONNECT BUS LENGTH:
5,000 FT. NO. 18AWG OR LARGER DUAL CONDUCTOR CABLE.
ALL WIRING MUST CONFORM TO LOCAL ELECTRICAL CODES.
RELAY CONTACTS RATING: 0.5A 30VDC; 0.5A 30VAC
1012B/2012B Wiring Diagram
Ordering Information
Part No.
1012B
2012B
Description
Ionization smoke detector with relay, 12 VDC,
multiple station
Photoelectronic smoke detector with relay, 12 VDC,
multiple station
A77-727-01 12 VDC power supply, mounts to a 4″ square box,
2
1
/
8
deep
System Sensor Worldwide Distribution
In Canada:
System Sensor Canada
6581 Kitimat Road, Unit #7
Mississauga, Ontario
Canada L5N 3T5
Telephone: 905-812-0767
Fax: 905-812-0771
Page 2
In the United Kingdom:
System Sensor Europe, Ltd.
Horsham Gates III, North St.
Horsham, West Sussex
RH13 5PJ, United Kingdom
Telephone: 44-1403-276500
Fax: 44-1403-276501
In India:
System Sensor India
A-204 Maheshwari Nagar
Orkay Mills Lane
Andheri East, Mumbai 400093
Telefax: 91-022-8202564
In the Far East:
System Sensor
Pittway Far East, Ltd.
Suite 706, New T&T Centre
7 Canton Road
Tsimshatsui, Kowloon, Hong Kong
Telephone: 852-2730-9090
Fax: 852-2736-6580
A05-238-02