INSTALLATION AND MAINTENANCE INSTRUCTIONS
2100AT Photoelectronic
Smoke Detector with Fixed Heat
and Integral Temp-3 Sounder
Figure 1. Wiring diagram for the 2100AT detector:
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
IMPORTANT: OBSERVE POLARITY
Polarity must be observed on the power and remote annunciator connections.
+
INITIATING
LOOP
EOL
+
UL LISTED
COMPATIBLE
CONTROL
RA400Z
PANEL
REMOTE
ANNUNCIATOR
+
P
+
W
R
A
+
A
-
NOT
USED
OPTIONAL CLASS A WIRING
NOTE: Only one detector per zone shall be used, unless when in alarm the panel switches
the zone to a reverse polarity, noncurrent-limited power supply. The 2100AT
detector shall not be mixed with other 2-wire detector types on the same zone.
A78-2336-15
Specifications
Diameter:
Height (including mounting bracket):
Weight:
Operating Temperature Range
Operating Humidity Range:
Latching Alarm:
Audible Signal:
Heat Sensor:
Electrical Ratings
System Voltage (nominal):
Minimum:
Maximum:
Maximum Ripple Voltage:
Standby Current:
Alarm Ratings:
Reset Voltage:
Reset Time:
Start-up Time:
EOL Relay:
Special Considerations:
5.5 inches (140 mm)
2.05 inches (52 mm)
7.5 oz. (210 g)
32° to 100° F (0° to 38° C)
10% to 93% Relative Humidity, Noncondensing
Reset by momentary power interruption
85 dBA minimum when in alarm or with supply polarity reversed
135° F Fixed Temperature Electronic Thermistor
12 or 24 VDC
8.5 VDC
35 VDC
30% of nom. Voltage (peak to peak)
50
µ
A average, 100
µ
A maximum
29 mA typical at 12 VDC, 63 mA typical at 24 VDC, 100 mA maximum
(If used, the RA400Z Remote Annunciator operates within the specified detector
alarm currents.)
1.8 VDC minimum
0.6 seconds maximum
30 seconds maximum (after 60 sec. reset)
A77-716B, 12/24 VDC
NOTE: Only one detector per zone shall be used, unless when in alarm the panel
switches the zone to a reverse polarity, non-current limited power supply. For
panels that do not provide this feature, a reversing relay, such as System Sensor’s
RR-2, may be used. When utilized with the 2100AT, it allows for more than one de-
tector to be utilized on a loop. Some panels may require the use of programmable
outputs. Refer to System Sensor literature for further information on the RR-2.
The 2100AT detector shall not be mixed with other 2-wire detectors on the same
zone.
–Due to the built-in temporal pattern, use this detector only with a non-coded
power source.
1
I56-1145-05R
D200-69-00