Figure 1. Flush mounting of detector on 4-inch  
octagon box:  
Figure 2. Detector mounting bracket:  
TAMPER  
RESISTANT  
TAB  
A78-534-00  
A78-1411-00  
TO MAKE DETECTOR TAMPER RESISTANT,  
BREAK OFF TAB EXTENSION  
AT SCRIBED LINE  
Mounting Instructions  
system and all smoke alarms before the panel gives the  
required battery-low signal. When the battery-low signal is  
given, the battery should be capable of providing power for  
another 7 days, after which the backup battery should have  
enough energy left to allow a 4-minute alarm signal to be  
given by all connected smoke alarms.  
Each 2400 Series detector unit is supplied with a mounting  
bracket kit that permits several mounting techniques:  
1. Units may be mounted directly to a 3-inch or 4-inch octagonal,  
11/2 inch deep electrical box. (See Figures 1 and 2.)  
2. Units may be mounted to a 4-inch square electrical box by  
using plaster ring with the supplied mounting bracket kit.  
Wiring Installation Guidelines  
Tamper-proof Feature  
All wiring must be in compliance with the National  
Electrical Code and the applicable local codes, and any  
special requirements of the local authority having  
jurisdiction. Proper wire gauges should be used. The  
conductors used to connect smoke detectors to control  
panels and accessory devices should be color-coded to  
prevent wiring mistakes. Improper connections can prevent  
a system from responding properly in the event of a fire.  
For signal wiring (the wiring between interconnected  
detectors), wire no smaller than 18 AWG is recommended.  
Wire sizes up to 12 AWG may be used. For best system  
performance, the power (+and –) loop wires should be  
twisted pair and installed in separate grounded conduit or  
shielded cable to protect the loop from extraneous electrical  
interference. If a cable shield is provided, the shield con-  
nection to and from the detector must be continuous by  
using wire nuts, crimping, or soldering as appropriate for a  
reliable connection.  
This detector includes a tamper-proof feature that, when  
activated, prevents removal of the detector without the use  
of a tool. To activate this feature, cut off smaller tab at the  
scribe line on tamper-proof tab located on the detector  
mounting bracket (see Figure 2). Install the detector. To  
remove the detector from the bracket once the tamper-  
proof feature has been activated, depress the tamper-proof  
tab located in the slot on the mounting bracket and turn the  
detector counterclockwise for removal.  
Installation In Australia Only  
The installation temperature range for Australia is 5° to  
45°C and has been tested per the Australian Standard.  
Ignore installation temperatures specified for all other  
applications when installing detectors in Australia.  
Detectors should be installed by qualified technicians.  
Installation of a mains connected power supply unit must  
be performed by qualified electricians only. The primary  
power will be provided by a panel type system. A recharge-  
able battery is required as a backup to the external power  
supply in case of a mains failure. In standby operation, the  
backup battery (fully charged) must be capable of  
providing uninterrupted power for at least 7 days to the  
Wire connections are made by stripping about 3/8" of  
insulation from the end of the wire (use strip gauge molded  
in base), sliding the bare end of the wire under the  
clamping plate, and tightening the clamping plate screw.  
Do not loop the wire under the clamping plate.  
Figure 3. Class A or Class B wiring diagram for model 2412AT and 2424AT detectors used with four-wire  
control panels:  
D400-04-00  
2
I56-288-05