INSTALLATION AND MAINTENANCE INSTRUCTIONS
I56-0598-004R
B114LP Plug-in Detector Base
For use with the following smoke detectors:
US
- 1151, 2151, 2151T;
CANADA
- 1151A, 2151A, 2151TA;
EUROPE
- 1151E, 2151E
SPECIfICATIONS
Base Diameter:
Base Height:
Weight:
Mounting:
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
6.2 in (157 mm)
0.95 in (24 mm)
0.6 lb (274 g)
4˝ square box with or without plaster ring, minimum depth 1.5˝; 4˝ octagon box, minimum depth 1.5˝;
3
1
2
˝ octagon box, minimum depth 1.5˝; 3
1
2
˝ octagon box, minimum depth 1.5˝
Operating Temperature Range:
0°C to 49°C (32°F to 120°F)
Operating Humidity Range:
10% to 93% Relative Humidity Non-condensing
Electrical Ratings (includes base and detector)
System Voltage:
120 VAC, 60 Hz
Relay Contact Ratings Resistive Load:
Form A — 2.0A @ 30VAC/DC; Form C — 2.0A @ 30VAC/DC, 1.0A @ 125VAC
(If used, the RA400 Remote Annunciator and RTC operates within the specified detector system voltage)
Start-up Time (after 60 second reset): 36.0 seconds maximum
BEfORE INSTALLINg
Please thoroughly read the System Sensor manual I56-407,
Guide for Proper
Use of System Smoke Detectors.
This manual provides detailed information on
detector spacing, placement, zoning, wiring, and special applications, and is
available at no charge from System Sensor. (For installation in Canada, refer to
CAN/ULC-S524,
Standard for the Installation of Fire Alarm Systems
and CEC
Part 1, Sec. 32.)
NOTICE:
This manual should be left with the owner/user of this equipment.
IMPORTANT:
The detector used with this base must be tested and maintained
regularly following NFPA 72 requirements. The detector used with this base
should be cleaned at least once a year.
gENERAL DESCRIPTION
The model B114LP detector base is designed for use with System Sensor model
2151 photoelectronic and 1151 ionization detector heads. This four-wire base is
equipped with screw terminals for the connection of power, ground, relay connec-
tions, and an optional RA400Z remote annunciator. It also includes a resistor that
limits current when the associated smoke detector is in the alarm state.
MOUNTINg
The detector base mounts directly to 3
1
/
2
-inch and 4-inch octagon boxes and
4-inch square boxes, with or without plaster rings. To mount the base, remove
the decorative ring by rotating it in either direction to unhook the snaps before
separating the ring from the base. Use the screws supplied with the junction
box to attach the base to the box through the appropriate slots in the base.
Position the decorative ring around the base and rotate it in either direction
until the ring snaps into place (see
Figure 2).
BASE TERMINALS
NO.
FUNCTION
NO.
FUNCTION
8
9
10
11
nect smoke detectors to control panels and accessory devices should be color-
coded to reduce the likelihood of wiring errors. Improper connections can
prevent a system from responding properly in the event of a fire.
For signal wiring (the wiring between interconnected detectors), it is recom-
mended that the wire be no smaller than AWG 18. However, the screws and
clamping plate in the base can accommodate wire sizes up to AWG 12. The
use of twisted pair wiring for the power (+ and –) loop is recommended to
minimize the effects of electrical interference.
fIgURE 1. TERMINAL LAyOUT:
24VDC/24VAC
TERMINALS
BASE
TERMINALS
7
6
STRIP GAUGE
1
2
3
SHORTING
SPRING
4
5
TAMPER
RESISTANT TAB
12
13 14
C1025-00
fIgURE 2. MOUNTINg BASE TO BOx:
SNAP ON
DECORATIVE
RING
1
2
3
4
5
6
7
C.
N.O.
Remote Annunciator (+)
Test Coil (+)
Not Used
Remote Annunciator (–)
RTC (–)
Supervisory Relay
Form A Contacts
8
9
10
11
12
13
14
N.O.
N.O.
C.
C.
N.O.
N.C.
C.
Alarm Relay
Form A
Initiation
Contacts
Alarm Relay
Form C
Auxiliary Contacts
DETECTOR
BASE
SHORTING
SPRING
(NOT SUPPLIED)
SCREWS
INSTALLATION gUIDELINES
Allowable loop resistance is an important specification for control panels as
well as for smoke detectors and their bases. The alarm system cannot be ex-
pected to operate correctly if system components have incompatible allowable
loop resistances. Therefore, before beginning installation, refer to the control
panel manufacturer’s loop resistance specification to ensure that it is listed as
compatible with the System Sensor base and smoke detector being installed.
All wiring must be installed in compliance with the National Electrical Code
and all applicable local codes and any special requirements of the authority
having jurisdiction, using the proper wire size. The conductors used to con-
D150-02-00
1
(NOT SUPPLIED)
BOX
C0503-00
I56-0598-004R