INSTALLATION AND MAINTENANCE INSTRUCTIONS
I56-0612-005R
B401BH and B401BHA
Sounder Bases
Specifications
Base Diameter:
Base Height (less base and sensor):
Weight:
Operating Temperature Range:
Operating Humidity Range:
Electrical Ratings
Voltage:
Standby Current:
Alarm Current:
Maximum Ripple Voltage:
Start-up Capacitance:
Horn Input Current Requirement:
Sound Output:
volts.
6 inches (152 mm)
0.75 inches (19mm)
0.3 lb. (140 g)
14° to 140°F (–10° to +60°C)
10% to 95%, noncondensing
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
17 to 32 VDC
1.0 mA maximum
15 mA maximum
10% of supply voltage
200 µF
600 µA maximum
Greater than 90 dBa measured in anechoic room at 10 feet (3 meters), 24
85 dBa minimum measured in UL reverberant room.
Before Installing
Please thoroughly read the System Sensor manual I56-407,
Guide for Proper Use of System Smoke Detectors,
which
provides detailed information on detector spacing, place-
ment, zoning, wiring, and special applications. Copies of
this manual are available at no charge from System Sensor.
NFPA 72 and NEMA should be observed. (For installa-
tion in Canada, refer to CAN/ULC-S524,
Standard for the
Installation of Fire Alarm Systems
and CEC Part 1, Sec.
32.)
General Description
Models B401BH and B401BHA sounder bases are intended
for use with System Sensor 400 Series plug-in sensor heads
in conventional 2-wire plug-in systems. Refer to systems
manuals for the maximum allowable number of units per
loop. The B401BH requires an external 24VDC (nominal)
supply with reverse polarity capability. The connections of
the external supply (terminals 1 and 2) and the initiating
loop (terminals 3, 4, and 5) are isolated in the B401BH to
prevent electrical interaction between them.
NOTICE:
This manual should be left with the owner/user When the detector head’s visible LEDs are latched on for
of this equipment.
approximately 10 seconds, the associated horn sounds. A
loop of horns can be made to sound by reversing the polar-
IMPORTANT:
The detector used with these bases must ity of the external supply.
be tested and maintained regularly following NFPA 72
requirements. The detector used with these bases should
NOTE: When the associated system is NOT used as a sup-
be cleaned at least once a year.
plementary evacuation system, the external 24VDC
supply must be treated as a component of the main
power supply system with the result that it falls
under the requirements of NFPA 72.
D400-50-00
1
I56-0612-005R