Watertight
4-Wire Photoelectric
Duct Smoke Detector
The InnovairFlex
Series are the only duct smoke
detectors flexible enough to fit configurations from
square to rectangular and everything in between.
Features
• NEMA Type 4 UL listed for non-hazardous indoor and outdoor applications
• UV Resistant, UL listed housing and cover material
• Photoelectric, integrated low-flow technology
• Air velocity rating from 100 ft/min to 4,000 ft/min (0.5 m/s to 20.32
m/sec)
• Versatile mounting options: square or rectangular configuration
• Plug-in sensor offers superb false alarm immunity and the latest
sensor technology
• Broad ranges for operating temperature (–4°F to 158°F) and
humidity (0% to 95% non-condensing)
• Patented sampling tube installs from front or back of the detector
with no tools required
• Increased wiring space with a newly added ¾-inch conduit
knockout
• One easy-access Test/Reset button and improved LED status
• Patented interconnect feature for multi-fan shutdown
• New high contrast terminal designations
• Built-in short circuit protection from operator wiring errors
• Field selectable settings for configuring the detector
• Two DPDT Form-C relay contacts
• 24 VAC/DC or 120VAC
• Backward compatibility with existing Innovair products, including
remote accessories
The InnovairFlex D4120W
watertight 4-wire photoelectric duct
smoke detector is UL listed as a watertight enclosure providing
protection against falling dirt, rain, windblown dust, splashing
and hose directed water. D4120W duct smoke detector features
a pivoting housing that fits various applications: both square and
rectangular footprints mount to round or rectangular ductwork.
This unit senses smoke in the most challenging conditions, operating
in airflow speeds of 100 to 4,000 feet per minute, temperatures
of –4°F to 158°F, and a humidity range of 0 to 95 percent (non-
condensing). A plug-in sensor head offers superior false alarm
immunity. These features, plus a NEMA 4 rating, allow operators to
mount the detector to rooftop HVAC equipment or use the detector
in other harsh environments.
The new design provides the same form, fit, and wiring terminations
as the standard InnovairFlex unit. Superior test and operational
features added to the standard model are also available in this
watertight unit. As the only watertight duct smoke detector on the
market, D4120W provides unsurpassed environmental protection
while simplifying installation, testing, and maintenance.
This InnovairFlex duct smoke detector can be customized to meet
local codes and specifications without additional wiring. The new
InnovairFlex product line is compatible with all previous Innovair
models, including remote test accessories.
WARNING:
Duct smoke detectors are
NOT
a substitute for open
area smoke detectors;
NOT
a substitute for early warning detection;
NOT
a replacement for a building’s regular fire detection system.
Refer to NFPA 72 and 90A for additional information.
NOTE:
To maintain the watertight properties of this duct smoke detector, watertight
conduit and fittings must be used. Mount the product with the conduit holes facing
downwards, if possible
Agency Listings