欢迎访问ic37.com |
会员登录 免费注册
发布采购

DH500 参数 Datasheet PDF下载

DH500图片预览
型号: DH500
PDF下载: 下载PDF文件 查看货源
内容描述: 智能管道烟雾探测器 [Intelligent Duct Smoke Detector]
分类和应用:
文件页数/大小: 2 页 / 418 K
品牌: SYSTEMSENSOR [ SYSTEMSENSOR ADVANCED IDEAS. ]
 浏览型号DH500的Datasheet PDF文件第1页  
continued
supply to the NAC will not be allowed to close if a short circuit condition
currently exists on the NAC. In addition, an algorithm is incorporated to find a
short when the module is active. The module will close all circuits that are not
shorted to find the NAC with the problem.
SYNC-1 ACCESSORY CARD
The SYNC-1 is an optional accessory to the SC-6 and is designed to provide
a means of synchronizing a series of horns, strobes, and horn/strobes. The
SYNC-1 is able to synchronize the temporal-coded horns, the one second
flash timing of the strobe, and silencing the horns of the horn/strobe
combination over a two-wire circuit while leaving the strobes active. Each
SYNC-1 accessory card has the capability of synchronizing six Class B circuits
or three Class A circuits.
CZ-6 SIX ZONE INTERFACE MODULE
The CZ-6 Six Zone Interface module provides an interface between the
intelligent alarm system and a two-wire conventional detection zone. A
common SLC input is used for all modules, and the initiating device circuits
share a common external supply. Otherwise, each module operates
independently from the others. The first module is addressed from 01 to 94
while the remaining modules are assigned to the next five higher addresses.
Provisions are included for disabling a maximum of two unused modules.
All two-wire detectors being monitored must be two-wire compatibility
listed with the modules. The CZ-6 transmits the status of a zone of two-wire
detectors to the fire alarm control panel. Status conditions are reported as
normal, open or alarm. The interface module supervises the zone of detectors
and the connection of the external power supply.
IM-10 TEN INPUT MONITOR MODULE
The IM-10 Ten Input Monitor module provides an interface between a
control panel and normally open contact devices such as pull stations,
security contacts, or flow switches. The first address is set from 01 to 90 and
the remaining modules are automatically assigned to the next nine higher
addresses. Provisions are included for disabling a maximum of two unused
addresses. The supervised state (normal, open or short) of the monitored
device is sent back to the panel.
500 Series Module Specifications
General Specifications
Operating Voltage
15 to 32 VDC
Maximum SLC Wiring Resistance
40 Ohms
Temperature Range
32°F to 120°F (0° to 49°C)
Relative Humidity
Wire Gauge
Dimensions
Specifications: CR-6
Standby Current
Alarm Current
10% to 85% noncondensing
12 to 18 AWG
6.8˝H × 5.8˝W × 1.25˝D
Specifications: IM-10
Standby Current
Alarm Current
3.5 mA maximum
60 mA maximum (assumes all ten LEDs
solid on)
Maximum IDC Wiring Resistance
40 Ohms
Maximum IDC Voltage
12 VDC
Maximum IDC Current
1 mA
1.45 mA maximum
32 mA maximum (assumes all six relays
have been switched once and all six
LEDs solid on)
Maximum IDC Wiring Resistance
40 Ohms
Relay Current
Relay Contact Ratings
Specifications: CZ-6
Standby Current
Alarm Current
30 mA/Relay Pulse (15.6 mS pulse
duration) pulse under panel control
30 VDC; 70.7 VAC
2 mA maximum
40 mA maximum (assumes all six LEDs
solid on)
Accessories
SYNC-1 Accessory Card
Maximum IDC Wiring Resistance
25 Ohms
External Supply Voltage
DC Voltage: 18 to 28 volts power
limited
Ripple Voltage: 0.1 volts RMS maximum
Current: 90 mA per circuit
Compatible Detectors
Specifications: SC-6
Standby Current
Alarm Current
Contact System Sensor for a current list
2.25 mA maximum
35 mA maximum (assumes all six relays
have been switched once and all six
LEDs solid on)
40 Ohms
63 W @ 70.7 VAC
30 VDC; 110 VAC
BB-6 Enclosure with CH-6 Chassis
Specifications: SYNC-1
Operating Voltage
Maximum Load on a Loop
Standby Current
11 to 30 VDC
Class A/Style Z: 3A
Class A/Style Y: 3A per pair
+0 Position: 15 mA
+2 or +4 Position if connected to
supply: 2.5 mA
12˝H × 9˝W × 3.67˝D
24˝H × 12.55˝W × 6.47˝D
Maximum NAC Circuit Wiring
Resistance
Power Rating Per Circuit
Relay Contact Ratings
Specifications: BB-2 Enclosure
Dimensions
Specifications: BB-6 Enclosure
Dimensions
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
©2008 System Sensor.
Product specifications subject to change without notice. Visit systemsensor.com for
current product information, including the latest version of this data sheet.
A05-0344-003 • 1/09 • #2088