欢迎访问ic37.com |
会员登录 免费注册
发布采购

LFD25-73MM 参数 Datasheet PDF下载

LFD25-73MM图片预览
型号: LFD25-73MM
PDF下载: 下载PDF文件 查看货源
内容描述: 低流速水流探测器 [Low Flow Rate Waterflow Detectors]
分类和应用:
文件页数/大小: 2 页 / 121 K
品牌: SYSTEMSENSOR [ SYSTEMSENSOR ADVANCED IDEAS. ]
 浏览型号LFD25-73MM的Datasheet PDF文件第2页  
Accuflow
Series
Low Flow Rate
Waterflow Detectors
Models Available
LFD20
LFD25-73MM
LFD25-76MM
LFD30-2
LFD40
Replacement Par ts
WFDW
546-9000
WFDN4
Cover wrench
Cover tamper
switch kit
Gasket kit
LFD30-2 (cover removed)
LFD30-2
Product Overview
For use in wet pipe water mist systems
Compatible with 2 to 4 inch stainless
steel and brass pipe
Solid state retard assures precise
timing accuracy
Dipswitch selections simplify
retard settings
Non-polarized, two-wire design
allows connection to a local bell and
conventional or addressable systems
NEMA 4 rated
Synchronized switches activate
both the alarm panel and local
bell simultaneously
System Sensor’s Accuflow
Low Flow Rate detectors are a new line of solid state
waterflow detectors designed for use in wet pipe water mist systems where low
flow detection is required.
Robust Construction.
Accuflow low flow detectors consist of a rugged enclosure for
indoor and outdoor use. Like all System Sensor waterflow detectors, low flow models
operate across a wide temperature range, from 32ºF to 120ºF (0°C to 49°C).
Reliable Performance.
Accuflow low flow detectors are intended for applications
where flow detection of 3 GPM or greater is required. By incorporating a solid state
retard, proper sensitivity, timing accuracy and switch resetting is assured.
False Alarm Immunity.
The solid state circuitry of Accuflow low flow detectors
provides greater timing accuracy over traditional mechanical retard designs. This
accuracy minimizes the risk of false alarms created by pressure surges or air trapped
within the sprinkler system.
Simplified Operation.
Accuflow low flow detectors are designed to simplify installa-
tion. Wired like traditional waterflow detectors, these models do not require the
installer to run an additional third wire. Two conduit openings permit easy attach-
ment to the local alarm system.
®