欢迎访问ic37.com |
会员登录 免费注册
发布采购

MDL 参数 Datasheet PDF下载

MDL图片预览
型号: MDL
PDF下载: 下载PDF文件 查看货源
内容描述: 同步电路模块 [Sync Circuit Module]
分类和应用:
文件页数/大小: 2 页 / 968 K
品牌: SYSTEMSENSOR [ SYSTEMSENSOR ADVANCED IDEAS. ]
 浏览型号MDL的Datasheet PDF文件第1页  
Sync•Circuit
Module Specifications
Architectural/Engineering Specifications
Synchronization Circuit Module shall be a System Sensor Sync•Circuit Model _________ listed to UL464 and shall be approved for fire protective service. The
module shall synchronize SpectrAlert® strobes at 1 Hz and horns at temporal 3. Also, the module shall be capable of silencing the horns on horn/strobe models,
while operating the strobes, over a single pair of wires. The module shall be capable of mounting to a 411⁄16˝× 411⁄16˝× 21⁄8˝ back box and shall control two Style Y
(class B) or one Style Z (class A) circuit. The module shall be capable of multiple zone synchronization by connecting multiple modules together via a slave-in/
slave-out arrangement and re-synchronizing each other along the chain. Note: The module shall not operate on a coded power supply.
Physical Specifications
Dimensions
51⁄4˝ L × 51⁄4˝ W
Mounting
Indoor Operating Temperature
Electrical/Operating Specifications
Operating Voltage
Operating Voltage Range (12 V)
Operating Voltage Range (24 V)
Maximum Load on Loop
U.S. Patent Nos.
411⁄16˝ × 411⁄16˝ × 21⁄8˝ back box
32° to 120° F (0° to 49° C)
12 or 24 VDC and FWR unfiltered
9 to 17.5 VDC
17 to 33 VDC
3 Amps/zone
HORNS
5,598,139
SILENCED OVER TWO WIRE CIRCUIT
MASTER MODULE HORN CONTROL CONNECTS
5,850,178
TO INTERRUPTABLE POWER SOURCE
Horns and Chimes Silenced Over Two-Wire Circuit
1. Any mix of Horn/Strobes, Chime/Strobes or Strobe only devices is acceptable
2. Horn and chime control connects to interruptible power source
MASTER MODULE
FACP #1
NAC1
SLAVE MODULE
(+)
(–)
EOL
(+)
(–)
NAC2
(+)
(–)
(+)
(–)
NAC3
(+)
(–)
(+)
(–)
(+)
(–)
}
}
}
}
HORN
CONTROL
ZONE 1
OUT
ZONE 1
IN
ZONE 2
OUT
ZONE 2
IN
SYNC
ERROR
SLAVE
IN
SLAVE
OUT
}
}
}
}
FACP #2
TO NEXT
SPECTRALERT
DEVICE OR
EOL
)+(
)–(
)+(
)–(
)+(
)–(
NAC1
(+)
(–)
(+)
(–)
)+(
)–(
)+(
)–(
TO NEXT
SPECTRALERT
DEVICE OR
EOL
NAC2
(+)
(–)
(+)
(–)
(+)
(–)
}
}
}
}
HORN
CONTROL
ZONE 1
OUT
ZONE 1
IN
ZONE 2
OUT
ZONE 2
IN
SYNC
ERROR
SLAVE
IN
SLAVE
OUT
}
}
}
}
)+(
)–(
)+(
)–(
TO NEXT
SPECTRALERT
DEVICE OR
EOL
)+(
)–(
)+(
)–(
TO NEXT
SPECTRALERT
DEVICE OR
EOL
TEMP JUMPER OFF
TEMP JUMPER OFF
All SpectrAlert horns,
horn/strobes, and strobes
will operate in sync.
Current Draw and Ordering Information
Red
MDL,
MDLA (Canadian)
White
MDLW,
MDLWA (Canadian)
Voltage
12
24
Average Current (mA)
DC
FWR
10
12
11
15
Peak Current (mA)
DC
FWR
30
31
35
37
In-rush Current (mA)
DC
FWR
87
122
198
262
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
©2007 System Sensor.
Product specifications subject to change without notice. Visit systemsensor.com for
current product information, including the latest version of this data sheet.
A05-1007-005 • 6/07 • #1676