General Description
All PS12/24ADA Series integrated sounder/strobes are
suitable for primary signaling in public mode life safety
applications. The sounder/strobes can be connected to the
alarm indicating circuit of a UL listed fire alarm control
panel. They are compatible with DC line supervision.
Panels may have full-wave rectified, unfiltered power
supplies. The sounder/strobes are available for either
24VDC operation, with 15, 15/75, 75, or 110 cd light
intensity, or for 12VDC operation with 15 or 15/75 cd light
intensity. They feature low current draw with no
measurable in-rush in excess of peak current. The
sounder/strobe is intended for wall mounting only to a 2″
electrical backbox. Mounting to a 4″ square electrical
backbox can be done with the addition of the PS-FP
accessory mounting plate.
Electrical Ratings – Strobe/Mini Horn
Model
Red
PS2415ADA
PS241575ADA
PS2475ADA
PS24110ADA
PS1215ADA
PS121575ADA
White
PS2415ADAW
PS241575ADAW
PS2475ADAW
PS24110ADAW
PS1215ADAW
PS121575ADAW
Supply
Voltage Range
20–30VDC
20–30VDC
20–30VDC
20–30VDC
10.5–17VDC
10.5–17VDC
Peak
Operating Current
(mA)
180
220
400
500
380
560
In-rush Current in
Excess of Peak
Operating Current (mA)
0
0
0
0
0
0
Average Operating
Current from
Regulated Supply
(mA)
90
108
185
225
185
240
Average Operating
Current from Full Wave
Rectified, Unfiltered Supply
(mArms)*
105
135
215
260
212
285
* For additional information, see installation manual D900-08-00.
Actual 12 volt operating voltage cannot be less than 8.5 VDC or greater than 18.7 VDC; actual 24 volt operating voltage cannot be less than 16 VDC or greater than 33 VDC.
Engineering Specifications
Sounder/Strobe shall be a System Sensor Model ______
listed to
Standard UL 1971 for the Hearing Impaired
and
shall be approved for Fire Protective Service. Sounder/
Strobe shall be wired as a Primary Signaling Notification
appliance. Sounder/strobe shall also comply with the
Americans with Disabilities Act requirements for visible
signaling appliances. Sounder/Strobe shall operate on 12
or 24VDC from a regulated DC supply or full-wave
rectified, unfiltered supply. The sounder/strobe shall be
powered from a non-coded power supply. Sounder/Strobe
shall have no measurable in-rush current in excess of
operating peak current. Visual signaling devices are to be
installed in all non-sleeping/corridor and sleeping areas
per plans and specifications. The strobe light shall consist
of a xenon flash tube and associated lens/reflector system.
All sounder/strobes shall be capable of semi-flush wall
mounting to a standard 2″
×
4″
×
1
1
/
2
backbox, without a
separate mounting plate or to a 4″
×
4″
×
1
1
/
2
backbox
with a separate mounting plate.
Standard Light Distribution
Vertical Dispersion
ZERO AXIS
Degree
0
5-30
5
35
40
45
10
50
55
15
60
65
70
20
75
80
85
25
90
0
Percent of Rating
100
90
65
46
34
27
22
18
16
15
13
12
12
12
Horizontal Dispersion
Degree
0
5-25
30-45
50
55
60
65
70
75
80
85
–90˚
90
Percent of Rating
100
90
75
55
45
40
35
35
30
30
25
25
45˚
–45˚
W
A
L
L
LIGHT
90˚
WALL
90˚ 85 80 75 70 65 60 55
50
45
40
FLOOR
35
30
A polar light distribution in both horizontal and vertical directions is mandated for the strobes by the
Standard UL 1971 for the Hearing Impaired,
with
specific minimum intensity percentages as shown in the graphs above. With its specially designed lens/reflector system, the PS12/24ADA Strobe
Retrofit Plate Series meets or exceeds these requirements at all angles.