欢迎访问ic37.com |
会员登录 免费注册
发布采购

SP3R1224MC 参数 Datasheet PDF下载

SP3R1224MC图片预览
型号: SP3R1224MC
PDF下载: 下载PDF文件 查看货源
内容描述: 可选的输出壁挂音箱/频闪灯 [Selectable Output Wall Speaker/Strobes]
分类和应用:
文件页数/大小: 2 页 / 254 K
品牌: SYSTEMSENSOR [ SYSTEMSENSOR ADVANCED IDEAS. ]
 浏览型号SP3R1224MC的Datasheet PDF文件第1页  
Selectable Output Speaker/Strobe Specifications
Architectural/Engineering Specifications
Speaker/Strobe shall be a System Sensor Model _____________ listed to UL 1480 and UL 1971 and be approved for fire protective signaling systems. Speaker
shall be capable of operating at 25.0 or 70.7 nominal Vrms, and shall have a frequency range of 400 – 4000 Hz. Speaker shall have power taps that are selected
by shunts. The strobe shall consist of a xenon flash tube with associated lens/reflector system and operate on either 12V or 24V. The strobe shall also feature
selectable candela output, providing options for 15 or 15/75 candela when operating on 12V and 15, 15/75, 30, 75, or 110 when operating on 24V. The strobe
shall comply with the Americans with Disabilities Act requirement for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range.
Physical Specifications
Dimensions
Mounting
Indoor Operating Temperature
Strobe Specifications
Strobe Operating Voltage
Input Terminals
Operating Voltage Range
Operating Voltage Range w/Sync•Circuit
Module
Speaker Specifications
Input Voltage
Input Terminals
Frequency Range
47⁄8˝ × 8¼˝ × 2¼˝
4˝ × 4˝ × 21⁄8˝ back box
32°F to 120°F (0°C to 49°C)
12 or 24 VDC and FWR unfiltered
12 to 18 AWG
12V: 8–17.5V; 24V: 16–33V
12V: 9–17.5V; 24V: 17–33V
25.0 or 70.7 Vrms (nominal)
12 to 18 AWG
400–4000 Hz
The SP2 and SP3 Series are UL listed from 400 to 4000Hz. The SP2 Series will provide a flat (±10dB)
output from 100 to 15,000Hz. The SP3 Series will provide a flat (±10dB) output from 500 to 13,000 Hz.
¼, �½, 1 and 2 watts
6,049,446; 6,127,935
2 Watts
84
89
1 Watt
81
87
�½ Watt
78
84
¼ Watt
75
81
Power Taps
U.S. Patent No.
Sound Output (UL Reverberant @ 10ft.)
SP2
SP3
Reversible Strobe Feature
Removing the strobe screw and lifting the strobe assembly out of the rib slot
allows the strobe to be rotated 180° and remounted to the base resulting in a
left-mounted strobe configuration.
INSERT SCREWDRIVER
TO REMOVE
Explanation of Published Strobe
Specifications
In May 2004, Underwriters Laboratories changed standard UL 1971 to
require that operating current measurements are made using RMS (root
mean square) instead of peak or average values. RMS measurements more
accurately predict the power consumption of a device since they take into
account the entire current draw profile including surge, repetitive surge, and
peak values. The published RMS current is the maximum operating current of
that device within its operating voltage range. This current maximum may or
may not occur at the endpoints of the voltage range.
In May 2004, UL also changed the way they list the voltage range of a device.
All 12V products will be listed between 8–17.5V and all 24V products will
be listed between 16–33V. These devices are considered “regulated.” Any
product that does not operate within these ranges will be listed as a “special
application” with its operating voltage specified on the device.
LOCKING RIB
Ordering Information/Current Draw
Model No.
Description
Wall Speaker/Strobe
Red
SP2R1224MC
SP3R1224MC
White
SP2W1224MC
SP3W1224MC
Candela Setting
15
15/75
30
75
110
UL Max. FWR Operating
Current–Strobe (mA RMS)
8–17.5V
16–33V
112
64
135
74
n/a
93
n/a
158
n/a
208
UL Max. DC Operating
Current–Strobe (mA RMS)
8–17.5V
16–33V
127
59
127
69
n/a
90
n/a
160
n/a
209
Accessories
BBS-SP2R
BBS-SP2W
Surface-mount back box skirt, red
Surface-mount back box skirt, white
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
©2006 System Sensor.
Product specifications subject to change without notice. Visit systemsensor.com for
current product information, including the latest version of this data sheet.
A05-0339-007 • 7/06 • #1676