欢迎访问ic37.com |
会员登录 免费注册
发布采购

PBA150F-48 参数 Datasheet PDF下载

PBA150F-48图片预览
型号: PBA150F-48
PDF下载: 下载PDF文件 查看货源
内容描述: [PBA150F]
分类和应用:
文件页数/大小: 1 页 / 102 K
品牌: TOTAL-POWER [ TOTAL POWER INTERNATIONAL ]
   
Unit type
Ordering information
PBA150F
R
PBA 150
1
2
3
F
4
-5
5
-O
1Series name
2 Output wattage
3 Universal input
4 Output voltage
5 Optional
C :with Coating
G :Low leakage current
(0.15mA max / ACIN 240V)
E :Low leakage current
and EMI class A
(0.5mA max / ACIN 240V)
T :Vertical terminal block
J :Connector type
(Only -12,-15,-24,-36,-48)
R :with Remote ON/OFF
N :with Cover
(Only 24V UL508 is acquired)
N1 :with DIN rail
V :Output voltage setting
potentiometer external-
ly
Specification is changed at
option. Please consult us
details.
MODEL
MAX OUTPUT WATTAGE[W]
DC OUTPUT
PBA150F-3R3 PBA150F-5
99
150
3.3V 30A
5V 30A
PBA150F-9
150.3
9V 16.7A
PBA150F-12
156
12V 13A
PBA150F-15
150
15V 10A
PBA150F-24
156
24V 6.5A
PBA150F-36
154.8
36V 4.3A
PBA150F-48
158.4
48V 3.3A
SPECIFICATIONS
MODEL
VOLTAGE[V]
CURRENT[A]
FREQUENCY[Hz]
INPUT
EFFICIENCY[%]
PBA150F-3R3 PBA150F-5
PBA150F-9
PBA150F-12
PBA150F-15
AC85 - 264 1f or DC120 - 370 (AC50 or DC70 optionally available *4)
ACIN 100V
1.3typ
2.0typ
ACIN 200V
0.7typ
1.0typ
50/60 (47 - 63)
ACIN 100V
80typ
83typ
ACIN 200V
82typ
86typ
0.98typ
0.99typ
0.87typ
0.93typ
20typ (Io=100%) (At cold start)
40typ (Io=100%) (At cold start)
0.4/0.75max (ACIN 100V/240V
3.3
5
30
30
20max
20max
40max
40max
80max
80max
140max
140max
120max
120max
160max
160max
PBA150F-24
PBA150F-36
PBA150F-48
82typ
85typ
83typ
86typ
84typ
87typ
85typ
88typ
85typ
88typ
85typ
88typ
OUTPUT
ACIN 100V
POWER FACTOR(Io=100%) ACIN 200V
ACIN 100V
INRUSH CURRENT[A]
ACIN 200V
LEAKAGE CURRENT[mA]
VOLTAGE[V]
CURRENT[A]
LINE REGULATION[mV]
LOAD REGULATION[mV]
0 to +50C
*1
RIPPLE[mVp-p]
-10 - 0C
*1
0 to +50C
*1
RIPPLE NOISE[mVp-p]
-10 - 0C
*1
TEMPERATURE REGULATION[mV]
60Hz, Io=100%,
9
16.7
36max
100max
120max
160max
150max
180max
According to IEC60950-1)
12
15
13
10
48max
60max
100max
120max
120max
120max
160max
160max
150max
150max
180max
180max
120max
150max
48max
150max
180max
60max
24
6.5
96max
150max
120max
160max
150max
180max
240max
290max
96max
36
4.3
144max
240max
150max
200max
250max
300max
360max
450max
144max
48
3.3
192max
240max
150max
200max
250max
300max
480max
600max
192max
0 to +50C
50max
50max
90max
-10 to +50C
60max
60max
120max
DRIFT[mV]
*2
20max
20max
36max
START-UP TIME[ms]
350typ(ACIN 100V, Io=100%)
HOLD-UP TIME[ms]
20typ (ACIN 100V, Io=100%)
OUTPUT VOLTAGE ADJUSTMENT RANGE[V]
2.85 - 3.63
4.00 - 5.50
7.50 - 10.0
OUTPUT VOLTAGE SETTING[V]
3.20 - 3.40
4.90 - 5.20
8.70 - 9.30
OVERCURRENT PROTECTION
Works over 105% of rated current and recovers
10.0 - 13.2
11.5 - 12.5
automatically
13.2 - 18.0
14.5 - 15.5
19.2 - 27.0
23.5 - 24.5
28.8 - 39.6
35.5 - 36.5
39.0 - 53.0
47.0 - 49.0
5.75 - 7.00
11.5 - 14.0
15.0 - 18.0
20.0 - 25.0
30.0 - 37.0
PROTECTION OVERVOLTAGE PROTECTION[V]
4.00 - 5.25
CIRCUIT AND OPERATING INDICATION
LED (Green)
OTHERS
REMOTE SENSING
Optional (Only -3R3, -5 Option -K)
REMOTE ON/OFF
Optional (Required external power source)
INPUT-OUTPUT
-RC
*3
AC3,000V 1minute, Cutoff current = 10mA, DC500V 50MWmin (At Room Temperature)
INPUT-FG
AC2,000V 1minute, Cutoff current = 10mA, DC500V 50MWmin (At Room Temperature)
ISOLATION
OUTPUT-RC-FG
*3
AC500V 1minute, Cutoff current = 100mA, DC500V 50MWmin (At Room Temperature)
OPERATING TEMP.,HUMID.AND ALTITUDE
-10 to +71C (Required Derating), 20 - 90%RH (Non condensing) 3,000m (10,000feet) max
STORAGE TEMP.,HUMID.AND ALTITUDE
-20 to +75C, 20 - 90%RH (Non condensing) 3,000m (10,000feet) max
ENVIRONMENT
VIBRATION
19.6m/s
2
(2G), 10 - 55Hz, 3minutes period, 60minutes each along X, Y and Z axis
IMPACT
AGENCY APPROVALS
SAFETY AND CONDUCTED NOISE
NOISE
REGULATIONS CE MARKING
HARMONIC ATTENUATOR
OTHERS
CASE SIZE/WEIGHT
COOLING METHOD
196.1m/s
2
(20G), 11ms, once each X, Y and Z axis
UL60950-1, C-UL(CSA60950-1), EN60950-1, EN50178 Complies with DEN-AN (At only AC input)
Complies with FCC Part15 classB, VCCI-B, CISPR22-B, EN55011-B, EN55022-B
Low Voltage Directive, EMC Directive
Complies with IEC61000-3-2
34X93X168mm (without terminal block) (WXHXD) / 560g max (without cover)
Convection
*
*
*
Parallel operation with other model is not possible.
Derating is required when operated with cover.
A sound may occur from power supply at peak loading.
43.0 - 50.0
58.0 - 65.0
*1
Measured by 20MHz oscilloscope or Ripple-Noise meter(equivalent to KEISOKU-GIKEN :
RM101).
*2
Drift is the change in DC output for an eight hour period after a half-hour warm-up at 25C.
*3
Applicable when Remote ON/OFF(optional) is added. RC is insulated with input, output and
FG.
*4 Derating is required.Consult us for details.