Industrial Power Supplies
TIS Series
75-600 Watt
Input Specifications
Input voltage range
– TIS 75, TIS 150, TIS 300, TIS 600
– TIS 500
– TIS 300 DCI
Input frequency
Input current at full load (typ.)
– TIS 75
– TIS 150
– TIS 300
– TIS 500
– TIS 600
Inrush current (< 2 ms)
– TIS 75
– TIS 150
– TIS 300
– TIS 500
– TIS 600
< 70
A
47 – 63 Hz
115 VAC
1.7 A
3.0 A
5.4 A
10.5 A
115 VAC
< 16.5 A
< 35
< 35
A
A
230 VAC
0.9 A
1.7 A
3.3 A
5.5 A
6.4 A
230 VAC
< 33 A
< 70 A
< 70 A
< 70 A
< 80 A
93 – 132 VAC / 187 – 264 VAC
187 – 264 VAC
300 – 800 VDC
Output Specifications
Output voltage adj. range
–
–
–
–
–
12
24
28
48
72
VDC
VDC
VDC
VDC
VDC
models
models
models
models
models
– TIS 75, TIS 150
– TIS 300, TIS 500, TIS 600
12
24
28
48
60
–
–
–
–
–
14
28
32
52
76
VDC
VDC
VDC
VDC (48 – 55 VDC on request))
VDC
Regulation
– Input variation
– Load variation (10 – 90 %)
± 0.2 % max.
± 1.0 % max.
± 0.3 % max.
(± 1.5 % in parallel operation)
< 50 mV pk-pk
current limitation at 110 % typ.
(constant current, automatic restart)
140 % typ. Vout nom.
115 VAC
min. 25 ms
min. 15 ms
230 VAC
min. 30 ms
min. 40 ms
min. 25 ms
Ripple and Noise
(20MHz Bandwidth)
Electronic short circuit protection
Overvoltage protection, triggerpoint at
Hold-up time
– TIS 75 ... TIS 300
– TIS 500
– TIS 600
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
http://www.tracopower.com