Industrial Power Supplies
TIS Series
75-600 Watt
DC-UPS-System
Battery +
Con3 - Pin2
V Battery Charger
Battery -
Con3 - Pin1
I
115/230VAC
L
Con1
Pin3
N
Con1
Pin2
Output
OK
DC
Con2 - Pin1/2
-Vout
Con1
Pin1
VBat>18V
Bat ON/OFF
Mains Fail
Battery Switch
Logic
Con4
Pin8
Con4 - Pin3
Battery
ON/OFF
Con4 - Pin2
Con4 - Pin1
AC-Powerfail
Common
AC-Power OK
Con4
Pin7
Mains
Fail
Detection
(Relay A)
AC-Powerfail
Con4 - Pin6
Con4 - Pin5
Con4 - Pin4
Battery Low / failure
Common
Battery OK
Battery
Test
(Relay B)
Low Battery
Specifications
Charging current
(factory set)
– TIS 300-124 UDS
– TIS 600-124 UDS
1.2 A
2.4 A
0.15...1.5 A
0.25...2.5 A
< 50 mA
system switches off
relay A closed
(pin 2 – pin 3)
relay B closed
(pin 5 – pin 6)
60 VDC /0.36 A max.
output current reduction by 1.4 x battery charge current
Adjustment range of charging current
– TIS 300-124 UDS
– TIS 600-124 UDS
Holding current for charging battery atvoltage 27.3 VDC
Overload at short circuit during battery operation
AC-Powerfail signal
Low battery signal
Raiting per relay contact
During battery charge operation
Vin < 93 resp. < 187 VAC
Battery voltage below 22 V
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
http://www.tracopower.com
Page 7
24VDC
AC
Con2 - Pin3/4
+Vout