Catalogue Page
1SBC 101 150 S0201
Auxiliary Contact Blocks
Accessories for NF Contactor Relays
Technical Data
Types
1-pole CA4, 1-pole CC4, 4-pole CA4, 2-pole CAL4
Contact Utilization Characteristics according to IEC
Standards
IEC 60947-5-1 and EN 60947-5-1
Rated insulation voltage Ui acc. to IEC 60947-5-1
Rated impulse withstand voltage Uimp
Rated operational voltage Ue max.
Conventional thermal current Ith - θ ≤ 40 °C
Rated frequency limits
690 V
6 kV
24 ... 690 V
16 A
25 ... 400 Hz
24-127 V 50/60 Hz
220-240 V 50/60 Hz
400-440 V 50/60 Hz
500 V 50/60 Hz
Rated operational current Ie / AC-15
acc. to IEC 60947-5-1
6 A
4 A
3 A
2 A
690 V 50/60 Hz
2 A
Making capacity acc. to IEC 60947-5-1
Breaking capacity acc. to IEC 60947-5-1
Rated operational current Ie / DC-13
10 x Ie AC-15 acc. to IEC 60947-5-1
10 x Ie AC-15 acc. to IEC 60947-5-1
6 A / 144 W
2.8 A / 134 W
1 A / 72 W
24 V DC
48 V DC
acc. to IEC 60947-5-1
72 V DC
110 V DC
125 V DC
220 V DC
250 V DC
400 V DC
500 V DC
600 V DC
0.55 A / 60 W
0.55 A / 69 W
0.27 A / 60 W
0.27 A / 68 W
0.15 A / 60 W
0.13 A / 65 W
0.1 A / 60 W
10 A
Short-circuit protection gG type fuse
Rated short-time withstand current Icw
θ = 40 °C
for 1.0 s
for 0.1 s
100 A
140 A
Minimum switching capacity
with failure rate acc. to IEC 60947-5-4
12 V / 3 mA
10-7
Heat dissipation per pole at 6 A
0.1 W
Mechanical durability
Number of operating cycles
Max. switching frequency
10 millions operating cycles
3600 cycles/h
1200 cycles/h
900 cycles/h
for AC-15
for DC-13
Max. electrical switching frequency
Contact Utilization Characteristics according to UL/CSA
Standards
UL 508, CSA C22.2 N°14
Rated insulation voltage Ui
Max. rated voltage
Pilot duty
600 V
600 V AC, 600 V DC
A600, Q600
10 A
7200 VA
720 VA
AC thermal rated current
AC maximum volt-ampere making
AC maximum volt-ampere breaking
DC thermal rated current
DC maximum volt-ampere making-breaking
2.5 A
69 VA
Connecting Characteristics
Screw terminals
All terminals
(delivered in open position, screws of unused terminals must be tightened)
M3.5
Connecting capacity (min. ... max.)
1 x
2 x
1 x
2 x
1 x
2 x
L <
Rigid solid
1 ... 2.5 mm²
1 ... 2.5 mm²
0.75 ... 2.5 mm²
0.75 ... 2.5 mm²
0.75 ... 2.5 mm²
0.75 ... 1.5 mm²
8 mm
Flexible with non insulated ferrule
Flexible with insulated ferrule
Bars or lugs
L
6
1 or 2 x
Capacity acc. to UL/CSA
Stripping length
AWG 18 ... 14
10 mm
Degree of protection
acc. to IEC 60947-1 / EN 60947-1 and IEC 60529 / EN 60529
IP20
Screwdriver type
Tightening torque
Flat Ø5.5 / Pozidriv 2
1.2 Nm / 11 lb.in