98000 Series
LCD Hour Meters
20000 Series Deluxe AC Hour Meters
20000 Series Wiring Diagrams
120VAC Meter Applications
N
Single phase, 2 wire,
120V system:
Connect
power wire to one terminal
and neutral wire to opposite
terminal.
Single phase, 3 wire,
120/240V system:
Connect
any one power wire to one
terminal and the neutral wire to
the opposite terminal.
Three phase, 4 wire wye,
120/208V system:
Connect
any one power wire to one
terminal and the neutral wire
to the opposite terminal.
Three phase, 4 wire delta
with a high leg,
120/240V system:
Connect
any one of the two available
120V power wires to one
terminal of the meter and the
neutral wire to the opposite
teminal. Do not connect the high
leg (208V) to the meter.
Retainer Mount
LCD Meter
APPLICATIONS
•
•
•
•
•
•
•
•
•
•
•
•
•
Garden Tractors
Generators
Utility Vehicles
Construction Equipment
Material Handling Equipment
Recreational Vehicles
Medical
Electronic Panels
Rental Equipment
Boom Lifts
Pressure Washers
Sweepers
Test Equipment
Operating
Voltage
9 to 64 VDC
9 to 64 VDC
9 to 64 VDC
HM
Terminals
2 terminal
3 terminal
with enable
4 terminal
resettable
Part #
98311
98321
98301
Retainer Mount:
Panel cutout 1.45 x .95
rectangular opening*
Rectangular Retainer Mount
Operating
Voltage
108-132
108-132
108-132
108-132
216-264
216-264
216-264
VAC
VAC
VAC
VAC
VAC
VAC
VAC
N
HM
Hertz
50
50
60
60
50
50
60
Termination
Screw*
Blade**
Screw*
Blade**
Screw*
Blade**
Screw*
Part #
20174
20183
20116
20182
20171
20170
20177
N
Rectangular Retainer:
Panel cutout 1.45 x .95
rectangular opening*
HM
N
HM
Round Chrome Bezel
Operating
Voltage
9 to 64 VDC
9 to 64 VDC
9 to 64 VDC
240VAC Meter Applications
* Panel cutout dimensions are ± .010 tolerance
All dimensions shown in inches and (metric)
Terminals
2 terminal
3 terminal
with enable
4 terminal
resettable
Part #
98314
98324
98304
Flush Mount (Retainer) 2.27”:
Panel cutout 2.00
diameter opening*
HM
N
Single Phase, 2 wire,
240V system:
Connect
power wire to one terminal
and neutral wire to opposite
terminal.
Single phase, 3 wire,
120/240V system:
Connect
meter across two high sides of
the line. Do not connect the
neutral wire to the meter.
Three phase, 3 wire delta,
240V system:
Connect meter
across any two power lines.
Square Retainer Mount
Operating
Voltage
108-132
108-132
216-264
216-264
VAC
VAC
VAC
VAC
Hertz
50
60
50
60
Termination
Screw*
Screw*
Screw*
Screw*
Part #
20176
20115
20173
20179
HM
N
Square Retainer: Panel
cutout 1.45 x .95
rectangular opening*
HM
Three phase, 4 wire delta
with a high leg,
120/240V system:
Connect any one power wire to
one terminal of the meter.
Connect one of the remaining
two power lines to the opposite
terminal. Do not connect the
neutral wire to the meter.
* UL Listed, CSA Certified and CE Mark
** UL Recognized, CSA Certified and CE Mark
N
HM
Round Black Bezel
Operating
Voltage
9 to 64 VDC
9 to 64 VDC
9 to 64 VDC
Terminals
2 terminal
3 terminal
with enable
4 terminal
resettable
Part #
98312
98322
98302
* Panel cutout dimensions are ± .010 tolerance
All dimensions shown in inches and (metric)
CAUTION: Always make sure power is removed from equipment before working on
electrical circuits! Only qualified personnel should make electrical connections.
Damage to equipment and/or serious bodily injury can result from improperly made
electrical connections, or a failure to adhere to normal electrical safety guidelines.
Flush Mount (Retainer) 2.27”:
Panel cutout 2.00
diameter opening*
4