AHP270XXD Series
Dynamic Characteristics
-55°C < T
CASE
< +125°C, V
IN
=270V
unless otherwise specified.
Parameter
LOAD TRANSIENT RESPONSE
AHP27005D
Either Output
Amplitude
Recovery
Amplitude
Recovery
AHP27012D
Either Output
Amplitude
Recovery
Amplitude
Recovery
AHP27015D
Either Output
Amplitude
Recovery
Amplitude
Recovery
4, 5, 6
4, 5, 6
4, 5, 6
4, 5, 6
4, 5, 6
4, 5, 6
4, 5, 6
4, 5, 6
4, 5, 6
4, 5, 6
4, 5, 6
4, 5, 6
Group A
Subgroups
Test Conditions
Notes 2, 8
Load Step 50%
⇔
100%
Load Step 10%
⇔
50%
10%
⇒
50%
50%
⇒
10%
Load Step 50%
⇔
100%
Load Step 10%
⇔
50%
10%
⇒
50%
50%
⇒
10%
Load Step 50%
⇔
100%
Load Step 10%
⇔
50%
10%
⇒
50%
50%
⇒
10%
-450
-450
450
200
450
200
400
750
200
750
200
400
750
200
750
200
400
mV
µs
mV
µs
µs
mV
µs
mV
µs
µs
mV
µs
mV
µs
µs
Min
Nom
Max
Unit
-750
-750
-750
-750
LINE TRANSIENT RESPONSE
Amplitude
Recovery
TURN-ON CHARACTERISTICS
Overshoot
Delay
LOAD FAULT RECOVERY
LINE REJECTION
4, 5, 6
4, 5, 6
Notes 1, 2, 3
VIN Step = 160
⇔
400 Volts
Note 4
Enable 1, 2 on. (Pins 4, 12 high or
open)
Same as Turn On Characteristics.
MIL-STD-461D, CS101, 30Hz to
50KHz - Note 1
60
70
dB
50
5.0
75
10
120
%
ms
-500
500
500
mV
µs
Notes to Specifications:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
Parameters not 100% tested but are guaranteed to the limits specified in the table.
Recovery time is measured from the initiation of the transient to where Vout has returned to within
±1.0%
of
Vout at 50% load.
Line transient transition time
≥
100µs.
Turn-on delay is measured with an input voltage rise time of between 100V and 500V per msec.
Current limit point is that condition of excess load causing output voltage to drop to 90% of nominal.
Parameter verified as part of another test.
All electrical tests are performed with the remote sense leads connected to the output leads at the load.
Load transient transition time
≥
10µs.
Enable inputs internally pulled high. Nominal open circuit voltage
≈
4.0VDC.
Load current split equally between +Vout and -V out.
Output load must be distributed so that a minimum of 20% of the total output power is being provided by one of
the outputs.
Cross regulation measured with load on tested output at 30% of maximum load while changing the load on
other output from 30% to 70%.
All tests at no-load are performed after start-up of the converter. The converter may fail to start when the output
load is less than 1.0W. Under these circumstances, the converter’s start-up circuitry will continue to cycle until
an adequate load is present.
4
www.irf.com