E5CK-
-T
D
Ramp/Soak Process Controller
Advanced, 1/16-DIN Ramp/Soak
Process Controllers Ideal for
Worldwide Use
Offers one pattern of simple programming control, up to
four patterns with communications (16 steps per
pattern).
Water-resistant front face meets IP66/NEMA 4 (indoor
use).
Modular structure, one-stock type.
Heat/Cool control.
Serial communications (RS-232C and RS-485).
Temperature and analog inputs.
High-accuracy: 100 ms sampling (for analog input).
Conforms to international EMC and safety standards.
3-year warranty.
D
D
D
D
D
D
D
D
RC
Ordering Information
Order control output boards and option boards separately. A single output board and option board can be mounted to each base unit. For
example, for a relay control output, order the E53-R4R4 output board in addition to the E5CK-TAA1-500 Process Controller. Model with
-500 has a terminal cover for finger protection
J
Process Controllers
Stock Note:
Shaded models are normally stocked.
Description
Base unit with terminal cover
DIN size
1/16 DIN
/
(48 x 48 mm)
)
Supply voltage
100-240 VAC
Model
E5CK-TAA1-500 AC100-240
E5CK-TAA1 AC100-240
Note: Part numbers ending in -500 available at Omron USA, non -500 numbers available in Omron Canada only. Model with -500 has a
terminal cover for finger protection.
J
Optional Output Boards
Stock Note:
Shaded models are normally stocked.
Description
Relay/Relay
Relay/Pulse
y/
Relay/Linear current
y/
Relay/Linear voltage
Pulse/Pulse
/
Computer communications
p
Event input
Transfer output
Specifications
SPST/SPST, 5 A, 250 VAC
SPST, 5 A/NPN, 24 VDC
SPST, 5 A/PNP, 24 VDC
SPST, 5 A/4--20 mA
SPST, 5 A/0-20 mA
SPST, 5 A/0-10 VDC
NPN/NPN, 24 VDC
PNP/PNP, 24 VDC
RS-232C
RS-485
For remote set point
4 to 20 mA
Max. quantity
1
1
1
1
1
1
1
1
1
1
1
1
E53-R4R4
E53-Q4R4
E53-Q4HR4
E53-C4R4
E53-C4DR4
E53-V44R4
E53-Q4Q4
E53-Q4HQ4H
E53-CK01
E53-CK03
E53-CKB
E53-CKF
Model
Note: If the control period is less than 5 seconds, use an SSR (solid state relay) or pulse voltage output.
A--180
Ramp/Soak Process Controller
E5CK-