Product data sheet
Characteristics
XB5AA21
black flush complete pushbutton Ø22 spring
return 1NO unmarked
Main
Range of product
Harmony XB5
Product or component
type
Complete push-button
Device short name
Bezel material
XB5
Plastic
Plastic
22 mm
1
Fixing collar material
Mounting diameter
Sale per indivisible
quantity
Shape of signaling unit
head
Round
Type of operator
Operator profile
Spring return
Black flush unmarked
1 NO
Contacts type and com-
position
Contacts operation
Slow-break
Connections - terminals
Screw clamp terminals : 1 x 0.22...2 x 2.5 mm² with-
out cable end conforming to EN/IEC 60947-1
Screw clamp terminals : <= 2 x 1.5 mm² with cable
end conforming to EN/IEC 60947-1
Complementary
Height
42 mm
Width
30 mm
Depth
52 mm
Terminals description ISO n°1
Product weight
(13-14)NO
0.037 kg
Resistance to high pressure washer
Contacts usage
Positive opening
Operating travel
7000000 Pa at 55 °C,distance: 0.1 m
Standard contacts
Without positive opening
4.3 mm (total travel)
2.6 mm (NO changing electrical state)
Operating force
3.8 N (NO changing electrical state)
5000000 cycles
Mechanical durability
Tightening torque
Shape of screw head
0.8...1.2 N.m conforming to EN 60947-1
Slotted head compatible with flat Ø 5.5 mm screwdriver
Slotted head compatible with flat Ø 4 mm screwdriver
Cross head compatible with pozidriv No 1 screwdriver
Cross head compatible with Philips no 1 screwdriver
Contacts material
Silver alloy (Ag/Ni)
Short circuit protection
10 A cartridge fuse type gG conforming to EN/IEC 60947-5-1
10 A conforming to EN/IEC 60947-5-1
[Ith] conventional free air thermal current
[Ui] rated insulation voltage
[Uimp] rated impulse withstand voltage
[Ie] rated operational current
600 V (degree of pollution: 3) conforming to EN/IEC 60947-1
6 kV conforming to EN/IEC 60947-1
1.2 A at 600 V, AC-15, A600 conforming to EN/IEC 60947-5-1
0.55 A at 125 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.27 A at 250 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.1 A at 600 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
6 A at 120 V, AC-15, A600 conforming to EN/IEC 60947-5-1
3 A at 240 V, AC-15, A600 conforming to EN/IEC 60947-5-1
Jun 22, 2015
1