5SHX 19L6010
Gate Unit Data
Power supply
(see Fig. 18, 19)
Maximum rated values
Note 1
Parameter
Gate Unit voltage
(Connector X1)
Min. current needed to power
up the Gate Unit
Characteristic values
Symbol Conditions
V
GIN,RMS
AC square wave amplitude (15 kHz
- 100kHz) or DC voltage. No
galvanic isolation to power circuit.
I
GIN Min
Rectified average current
see application note 5SYA 2031
min
28
typ
max
40
Unit
V
2.1
100
min
typ
max
8
A
W
Unit
A
Gate Unit power consumption P
GIN Max
Parameter
Internal current limitation
Symbol Conditions
I
GIN Max
Rectified average current limited by
the Gate Unit
Optical control input/output
2)
(see Fig. 23)
Maximum rated values
Note 1
Parameter
Min. on-time
Min. off-time
Characteristic values
Symbol Conditions
t
on
t
off
Symbol Conditions
P
on CS
CS: Command signal
P
off CS
SF: Status feedback
Valid for 1mm plastic optical fiber
P
on SF
min
40
40
min
-15
-19
typ
max
Unit
µs
µs
Parameter
Optical input power
Optical noise power
Optical output power
Optical noise power
Pulse width threshold
External retrigger pulse width
typ
max
-1
-45
-1
-50
400
Unit
dBm
dBm
dBm
dBm
ns
ns
P
off SF
t
retrig
(POF)
t
GLITCH
Max. pulse width without response
600
1100
2) Do not disconnect or connect fiber optic cables while light is on.
Connectors
2)
(see Fig. 20 to 22)
Parameter
Gate Unit power connector
LWL receiver for command signal
LWL transmitter for status feedback
Symbol Description
3)
X1
AMP: MTA-156, Part Number 641210-5
CS
SF
Avago, Type HFBR-2528
Avago, Type HFBR-1528
4)
4)
2) Do not disconnect or connect fiber optic cables while light is on.
3) AMP, www.amp.com
4) Avago Technologies, www.avagotech.com
Visual feedback
(see Fig. 20)
Parameter
Gate OFF
Gate ON
Fault
Power supply voltage OK
Symbol Description
LED1 "Light" when GCT is off
LED2
LED3
LED4
"Light" when gate-current is flowing
"Light" when not ready / Failure
"Light" when power supply is within specified range
Color
(green)
(yellow)
(red)
(green)
ABB Switzerland Ltd, Semiconductors reserves the right to change specifications without notice.