Data Sheet  
QBK020A Series Power Modules; DC-DC Converters  
36 – 55 Vdc Input; 12Vdc Output; 20A Output Current  
March 27, 2008  
In all parallel applications (including applications  
meeting the [n-1] sizing criteria discussed earlier), if  
it is expected that a protective shutdown event could  
cause more than one parallel module to shutdown  
(for example, over temperature due to a common  
fan failure, or gross over current affecting two or  
more modules simultaneously), then the use of the  
auto-restart (4) option is not recommended. The  
auto-restart interval of these modules is not  
synchronized to other modules, nor is it precise.  
There will not be a successful restart following  
multiple module shutdowns, because the individual  
module’s restart timings will be different. There will  
not be sufficient module capacity to prevent the first  
module which restarts from experiencing an over  
current, and then again shutting down before the  
slowest module has restarted. Meanwhile, the  
slowest module will then restart, and then shutdown  
during the interval the fastest module is waiting for  
its next restart. And so on and so on. In these  
cases, only latching shutdown modules should be  
used; and either toggling the Vin source or the on/off  
pin to simultaneously restart the modules, following  
a shutdown, is advised.  
Feature Description (continued)  
Forced Load Sharing (Parallel Operation with –  
P option)  
For additional power requirements, the power module  
can be configured for parallel operation with active load  
current sharing. Good layout techniques should be  
observed for noise immunity when using multiple  
modules in parallel. To implement active load sharing,  
the following recommendations must be followed:  
The parallel pins of all units in parallel must be  
connected together. The path of these connections  
should be as direct as possible, but should not pass  
beneath the perimeter of the module body, except  
immediately adjacent to the parallel pin location.  
Parallel modules must use the same 48V source.  
The VIN (-) input pin is the return path for the active  
current share signal of the parallel pin. Separate  
48V sources will prevent the active current share  
return signal from being connected to other  
modules.  
The VIN (-) input connection should never be  
disconnected from any of the parallel modules, while  
another of the parallel modules is operating, unless  
the VIN (+) pin, or the parallel pin is also  
When not using the parallel feature, leave the share pin  
open.  
disconnected. The VIN (-) input provides the internal  
logic ground and for the module’s primary circuits,  
including the active current share circuit; and there  
are sneak paths through the module’s internal  
control ICs, when the VIN (-) pin is disconnected  
(allowing the internal logic circuit to float), while the  
parallel pin and VIN (+) pin are connected to other  
operating modules. These sneak paths do not cause  
permanent damage, but do create false conditions  
that can affect the module’s internal logic  
configuration.  
The on/off pins of all modules should also be tied  
together to the same external control circuitry, so  
that the modules are turned on and off at the same  
time, unless all parallel modules’ on/off pins are tied  
to the input pins for automatic start upon application  
of input voltage.  
When modules in parallel applications contain the  
auto-restart (4) option, it is required that the total  
maximum load current value be less than 90% of [n-  
1] times the individual module output current rating,  
where n is the number of modules in parallel. For  
example, if the application is using three modules  
rated at 20A, then the maximum total load shall be  
less than 0.9 x (3-1) x 20A = 0.9 x 2 x 20A = 36A.  
This insures that a single module can shutdown  
without causing the total load to exceed the  
capability of the remaining operating module(s). The  
shutdown module can then automatically restart,  
and assume its share of the total load.  