THERMATEL
TA2
L L L L L L L L L L L L L L L L L L L L
Product Features:
Accepts all typical input powers in same unit
Second mA output for temperature output or second flow range optional
Integral or remote electronics
Pre-calibrated and configured for the user’s application. Ready to install.
Flow totalization
All explosion proof housing with FM, FMc, and ATEX hazardous area approval
Insertion probes and flow body designs
SA
Pulse output optional
Rotatable housing to permit viewing the display from any position
Stainless steel and Hastelloy probes with wide selection of process connections
F
ET
Y
I
NT
EGRITY
Ability to replace probe/circuit boards in field
On-site calibration verification procedure
PACTware
™
for configuration, diagnostics, and trending
SIL 1 with SFF value of 88.4%
NIST traceable calibration
Optional hot tap assembly
HART
®
, AMS communication
Ability to replace probe in field
4-button keypad for data entry
Two gas calibrations available
APPROVALS
S P E C I F I C AT I O N S
Supply Voltage
Power Consumption
Flow Range Maximum
Accuracy Flow
Accuracy Temperature
Repeatability
Turn Down
Ambient Temperature
Process Temperature
Pressure Rating
Analog Output Signal
Active:
4–20 mA (isolated) maximum 1000
Ω
loop resistance
Passive:
4–20 mA (isolated) loop resistance dependent on power supply
HART
Optional
11.6 to 30 VDC
100 to 264 VAC
7 VA typical
10–50,000 SFPM (0.05–250 Nm/s) air reference to standard conditions
Higher ranges and other gases available
±1% of reading +0.5% of calibrated full scale
±2° F (1° C)
±0.5% of reading
100:1 typical (depending on calibrated flow range)
-40° to +176° F (-40° to +80° C);
display not readable below -22° F (-30° C)
-50° to +400° F (-45° to +200° C)
1500 psig (103 bar) maximum
V
EL
LE
7