The following configuration entries are the minimum
required for configuration. The default password is 0.
Blocking
Distance
8
6
2
3
4
17
Sensor Offset
5
1
14 15
13
11
12
Tank Height
7
9
Offset
Level
10
16
1
Units
(select)
Select the
Units
of measurement
for the level
readout (cm, inches, meters, feet).
Select the
Antenna Type
to be used
as printed on the transmitter name-
plate; first 7 digits of model number.
Select the
Antenna Extension
to
be used as printed on the antenna
nameplate; last 3 digits of model
number.
Select the type of
Antenna
Mounting
to be used.
Enter the
Sensor Offset
value; the
distance from the top (100%) point
of the vessel to the Sensor
Reference point (bottom of an NPT
thread, top of a BSP thread, face of
a flange).
Select the type of
Tank Top;
choic-
es are Flat, Horizontal cylinder,
Dome, Irregular, or Other (non-
metallic).
Enter the exact
Tank Height;
inac-
curate values will create inaccurate
level readings.
Enter the
Blocking Distance;
the
distance close to the antenna
where measurement is unreliable
due to antenna ringing.
Minimum value = antenna length +
2" (50 mm)
9
LevlOfst
xxx.x
2
Antna Typ
(select)
Enter the
Level Offset;
the distance
at the bottom of the vessel where
measurement may be unreliable
due to heating coils, irregular bot-
tom, etc.
Select the proper
Dielectric
range
for the process medium.
Select the value of
Turbulence
that
corresponds to the application.
Select the
Rate of Change
value
that corresponds to the maximum
rate the level will rise or fall.
Select the
Foam
value that corre-
sponds to the application.
Examine the list of reflections
detected by the transmitter to
ensure the actual level reflection is
present. It may be necessary to
rotate the launcher for optimum
performance.
Run the
Target Rejection
routine
by choosing the correct LEVEL
thereby cancelling all false reflections
in the vessel; ideally with tank empty.
Enter the minimum level value (0%)
for the 4 mA point.
Enter the maximum level (100%) for
the 20 mA point.
10
Dielectrc
(select)
Turbulnc
(select)
RateChg
(select)
3
Antna Ext
(select)
11
4
Antna Mnt
(select)
SnsrOfst
xxxx
12
5
13
Foam
(select)
Targets
14
6
Tank Top
(select)
15
TargRej
(status)
7
Tank Ht
xxxx
8
BlockDis
xxxx
16
Set 4mA
xx.x
Set 20mA
xx.x
17
Note: Clear all diagnostic messages upon completion
of configuration. See screens 41 and 42 on
page 24.
58-601 Pulsar
®
Radar Transmitter
8