MAP110 SERIES
ENVIRONMENTAL SPECIFICATIONS
PARAMETER
CONDITIONS/DESCRIPTION
MIN
NOM
MAX
UNITS
Altitude
Operating.
Non-operating.
10k
50k
ASL Ft.
ASL Ft.
Operating Temperature
Derate linearly above 50°C by 2.5% per° C
to a maximum temperature of 70°C.
At 100% load:
At 50% load:
0
0
50
70
°C
°C
Storage Temperature
Temperature Coefficient
Relative Humidity
-55
85
0.05
95
°C
%/°C
%RH
0°C to 70°C.
Non-condensing.
0.03
OPTIONS
DESCRIPTION
NOTES
DIMENSIONS
L-Bracket
Add ‘L’ suffix to model number.
7.15" x 4.50" x 2.40"
(182.0mm x 115.0mm x 61.0mm)
Cover
Add ‘C’ suffix to model number. Includes L-Bracket.
7.20" x 4.50" x 2.40"
(183.0mm x 115.0mm x 61.0mm)
Power Fail
Signal
Add ‘P’ suffix to model number. Provides >5 mS typical warning time before
main output drops 5%. Warning time increases at reduced load levels.
N/A
Thermal
Shutdown
Add ‘T’ suffix to model number. Initiates shut-down in the event of an overtemperature
condition. Automatic recovery.
N/A
NUCLEAR AND MEDICAL APPLICATIONS Power-One products are not authorized for use as critical components in life support systems,
equipment used in hazardous environments, or nuclear control systems without the express written consent of the President of Power-One, Inc.
TECHNICAL REVISIONS The appearance of products, including safety agency certifications pictured on labels, may change depending on the
date manufactured. Specifications are subject to change without notice.