CORCOM Product Guide
Enhanced Performance K Series RFI Power Line Filters
DK Series
DK3
UL Recognized
CSA Certified
VDE Approved
DK1
DK6
DK Series
Specifications
Maximum leakage current, each line-to-ground
VDK Models
The DK series RFI power line filters are general
purpose common mode and differential mode filters
with higher performance line-to-line attenuation than
the VK series.
EDK Models
.22 mA
.38 mA
@ 120 VAC 60 Hz:
@ 250 VAC 50 Hz:
.4 mA
.7 mA
Hipot rating (one minute):
The E version of the DK series (EDK) has the same high
performance line-to-line attenuation while still meeting the
very low leakage current requirements of VDE portable
equipment and UL544 non-patient care equipment.
line-to-ground
line-to-line
2250 VDC
1450 VDC
Operating frequency:
Rated voltage (max.):
50/60 Hz
250 VAC
The V version of the DK series (VDK) has the same high
performance in a more cost-effective package for
applications without strict leakage current requirements.
Rated current:
1VDK/1EDK
3VDK/3EDK
6VDK/6EDK
10VDK/10EDK
20VDK/20EDK
1A
3A
6A
10A
20A
Electrical Schematic
LOAD
LINE
Minimum insertion loss in dB:
Line-to-ground in 50 ohm circuit
Current
Rating
Frequency-MHz
.15 .5 10 30
1
5
Resistor location for reference only.
VDK Models
1A, 3A
6A, 10A, 20A
18 30 40 48 48 40
10 22 30 39 44 50
EDK Models
1A, 3A
6A, 10A, 20A
17 27 33 45 45 40
10 19 25 34 40 46
Line-to-line in 50 ohm circuit
Current
Frequency-MHz
Rating
.15 .5
1
5
10 30
VDK, EDK Models
1A, 3A
6A, 10A, 20A
18 47 62 60 50 45
20 43 55 65 60 55
22
Catalog 1654001
Revised 05-07
Dimensions are in inches and
Dimensions are shown for
USA Cust. Svc.: 1-800-468-2023
CORCOM Prods: 1-847-680-7400
Germany: 49-89-6089-0
www.corcom.com
www.tycoelectronics.com
millimeters unless otherwise
specified. Values in italics
are metric equivalents.
reference purposes only.
Specifications subject
to change.